Vanguard WRM-10 User Manual
Page 12

WRM-10 USER’S MANUAL
REV 2
9
3.0 OPERATING
PROCEDURES
3.1
WRM-10 Cable Connections
Typical WRM-10 connections diagrams are shown in Figure 5 and Figure 6. A typical dual
winding connections diagram is shown in Figure 7.
WARNING
Do not touch or disconnect any test lead that is connected to a transformer
terminal while high current is being conducted during a test. Failure to heed this
warning can result in lethal electric shock to personnel and/or damage to the
equipment.
Figure 5. Typical WRM-10 Connections Diagram #1
WARNING
Disconnect the test clips from the transformer bushing only after the WRM-10
has completely discharged the transformer. Always disconnect the test clips
slowly from the transformer bushing to prevent an accidental flash-over.