WRM-10 USER’S MANUAL

REV 2

5

Table 2. Functional Descriptions of WRM-10 Controls and Indicators

Item

Number

Panel Markings

Functional Description

1

V1

Voltage sensing input channel #1. Female connector jacks used for connecting
voltage-sensing test leads.

2

I

Current output. Female connector jacks used for connecting current test leads.

3

None

Back-lit LCD screen (16 characters by 2 lines); viewable in bright sunlight and
low-light levels.

4

GROUND

Safety ground terminal. 5/16-18 threaded stud with hand-turned wing nut. This
must be connected to the station ground before connecting any WRM-10 test
leads to the transformer.

5

100-120 Vac. 2A,

50-60 Hz

Fuse: 250 Vac, 3A

Slow-Blow

Input power connector with third-wire safety ground. On/Off rocker toggle switch
with built-in fuse protection.

6

RS-232C

9-pin RS-232C interface port; female DB type. Data rate is set to 19,200 baud,
1 start bit, 2 stop bits, 8 data bits and no parity bit.

Pin Signal
2 RX
3 TX
5 Signal

Ground

7

DISCHARGE

Red LED indicator light. This warning indicator is lit when the WRM-10 is
discharging the stored energy in the transformer. Do NOT disconnect the test
leads when this light is on. Failure to heed this warning can result in
shock and/or fatal injury to personnel.

8

CHANGE

“PUSH” TO

SELECT

Single turn-and-press control knob used to operate the WRM-10. You can scroll
through different menu options by turning this knob, and you can select a
function by pressing the knob.

9

HIGH VOLTAGE

PRESENT

Red LED indicator light. This warning light is illuminated when there is a
possibility of high voltage across the test leads. Do NOT disconnect the test
leads when this light is on. Failure to heed this warning can result in
shock and/or fatal injury to personnel.

10

V2

Voltage input sensing channel #2. Female connector jacks used for connecting
voltage-sensing test leads.