2.0 VBT SPECIFICATIONS

2.1 VBT-60 Specifications

VBT-60 specifications and leading particulars are listed in Table 1.0.

Table 1.0. VBT-60 Specifications

MODEL....................... VBT-60

TYPE ............................ Special-Purpose Test Equipment, portable 60 kV vacuum bottle tester

SIZE (inches) .............. 16.8 W by 3.5 H by 10.6 D (42.7 cm by 8.9 cm by 26.9 cm)

WEIGHT....................... 10 pounds (4.53 Kg)

INPUT POWER ........... 2 amps, 90-240 Vac, 50/60 Hz

OUTPUT VOLTAGE... 10kV to 60kV dc in 5,000 volt steps

OUTPUT RIPPLE
VOLTAGE
.................... 3% max

DISCHARGE TIME ..... Maximum discharge time for internal high voltage is 0.3 seconds

DISPLAY...................... Backlit LCD, 2-lines by 16 characters

INDICATORS ............. Test failure indicator: LED is turned on if test current exceeds

the preset current threshold (100

?

A, 200

?

A or 300

?

A).

High Voltage Enable Indicator: LED is turned on when high voltage
is present at high voltage cable.

CONTROL ................... Single knob selector (turn-and-press selection)

COMPUTER
INTERFACE
................ RS-232C port, 19,200 Baud (Factory Calibration and Diagnostic)

ENVIRONMENT.......... Operating: -10°C to 55°C (15

?

F to +122

?

F)

Storage: -30°C to 70°C (-22

?

F to +158

?

F)

FURNISHED ITEMS ... One power cord, one ground cable, one 10-ft. high-voltage cable,

One 10-ft. high-voltage return cable.

OPTIONS ................... Transportation case included

WARRANTY................ One-Year Parts & Labor (Post-Warranty Service Contracts Available)

VBT-60 SPECIFICATIONS ARE SUBJECT TO UPGRADES AND MAY BE CHANGED WITHOUT PRIOR NOTICE.