Oven gas requirements – XLT XD-9004A User Manual

Page 15

Advertising
background image

15

Technical Support US: 888-443-2751

Technical Support INTL: 316-943-2751

For Australia, if installing with a flexible hose assembly, the assembly must be certified to
AS/NZS 1869, & be Class B or D.

For Standard Ovens, if installing with a flexible gas hose, the installation must comply with
either ANSI Z21.69 or CAN/CGA-6.16 & a disconnect device complying with either ANSI
Z21.41 or CAN-6.9.

The installation must conform with local building codes, or in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1, latest version, Natural Gas Installation Code, CAN/
CGA-B149.1, or the Propane Installation Code, CAN/CGA-B149.2, as applicable.

1. The appliance & its individual shutoff valve must be disconnected from the gas supply piping

system during any pressure testing of that system at test pressures in excess of 3.5 kPa or ½-
psi.

2. The appliance must be isolated from the gas supply piping system by closing its individual

manual shutoff valve during any pressure testing of the gas supply piping system at test pres-
sures equal to or less than 3.45 kPa or ½-psi.

OVEN GAS REQUIREMENTS

Gas Supply Testing Requirements

Gas Hose Requirements

Advertising