Installation, Duty cycle – Lincoln Electric IM10119 IDEALARC AC-1200 User Manual

Page 11

Advertising
background image

A-4

INSTALLATION

IDEALARC

®

AC-1200

A-4

2. Output Studs

Connect the work cables to the “To Work” stud on
the front of the AC-1200. Connect the electrode
cables to the “Min”, “Med” or “Max” studs for the
output desired. Actual current ranges for each stud
are indicated on the nameplate above each stud.
Recommended cable sizes are listed below. Both
the “To Work” and “Max” studs have two terminals
to simplify connection of recommended cables in
parallel. Tighten the nuts with a wrench.

Select cables required for combined work and elec-
trode cable lengths up to 150ʼ from the following
table:

Maximum Allowable Current for Copper Welding Cable

Cables in accessory kit recommended below have
terminals as required to comply with applicable
U.L. standards for safety.

150ʼ combined length electrode and work cables.

3. Auxiliary Power

920 volt-amperes of 115 volt AC power are avail-
able from #31 and #32 on the AC-1200 terminal
strip.

DUTY CYCLE

The AC-1200 is rated for 100% duty cycle at 1200
amps and 44 volts.

Duty

Cycle

One 4/0

Two 4/0

Three 4/0

Four 4/0

100%

500

930

1150

1350

80%*

560

1040

1290

1510

* Based on 10 minute cycle.