Installation, Operation and Maintenance

Make sure you follow all the recommendations in the GP4000 Series
Installation Guide and additionally those listed below.

DANGER

POTENTIAL FOR EXPLOSION

Confirm that the location is free from explosively hazardous gases or
dust before connecting or disconnecting equipment, replacing or
wiring modules.

The ambient temperature in protective enclosure must not exceed
50°C or 55°C (refer to marking).

Confirm each interface (COM1, COM2, LAN), field wiring terminal
blocks and the SD Card / Battery Cover have been securely locked.

Confirm USB cables are attached with its appropriate clamp.

Modules must be installed in a protective enclosure that provides at
least the following degree of protection:
- IP54 for atmosphere with gas
- IP6x for atmosphere with dust

Do not open the protective enclosure while the system is powered up.

Confirm that the power supply has been turned OFF before
disconnecting, replacing or wiring modules.

Ensure that the FG (Functional Ground) on the power supply is
properly connected to ground.

Use only screw fasteners suitable for installations in explosive
atmospheres.

Do not use damaged equipment.

Use Touch Pen CA7-TPPEN/ALL-01 on all GP4000 Series used in
zone 2 and zone 22 areas.

Failure to follow these instructions will result in death or serious injury.