3 grounding, 3 grounding -21 – Proface APL3000B - Node Box PC User Manual

Page 76

Advertising
background image

Chapter 3 Installation and Wiring

3-21

3.3.3

Grounding

This section describes the precautions for grounding the PS-B unit.

• When supplying power to the PS-B unit, be sure to separate the

input/output and power lines, as shown. [diagram (a)]

• If exclusive grounding is not possible, use a common ground-

ing point. [diagram (b)] A grounding or equivalent should be

used for the grounding point.

Do not use common grounding, since it can lead to an accident or machine breakdown.

• Check that the grounding resistance is

100

Ω or less.

• FG and SG terminals are internally

connected in the PS-B. When

connecting an external device to the

PS-B using the SG terminal, be sure to

check that no short-circuit loop is

created when you setup the system.

• The grounding wire should have a cross

sectional area greater than 2mm

2

.

Create the grounding point as close to

the PS-B unit as possible, and make

the wire as short, as possible. When

using a long grounding wire, replace the

thin wire with a thicker wire, and place it

in a duct.

If the equipment does not function properly

when grounded, disconnect the ground wire

from the FG terminal.

(a) Exclusive Grounding (BEST)

(b) Exclusive Grounding (OK)

(C) Common Grounding (Not OK)

PS-B

PS-B

PS-B

Other

Equipment

Other

Equipment

Other

Equipment