Universal process, Mechanical relay form c, Solid-state relay form a – Watlow EZ-ZONE PM Express User Manual
Page 14: Switched dc, No-arc relay form a, Open collector, F1 h1 g1 negative volts + current

EZ-ZONE PM Express (PID)
• 14 •
Install and Wire
F1
H1
G1
negative
volts +
current +
4
Universal Process
PM _ C _ (F) _ - A A A A B _ _
L1
J1
K1
normally open
common
normally closed
Mechanical Relay
Form C
PM _ C _ (E) _ - A A A A B _ _
Solid-State Relay
Form A
L1 and/or L2
K1 and/or K2
PM _ C _ (K) (K) - A A A A B _ _
W1 and/or W2
dc +
dc -
Y1 and/or Y2
common
Switched DC
PM _ C _ (C) (C) - A A A A B _ _
L2
K2
NO-ARC Relay Form A
PM _ C _ _ (H) - A A A A B _ _
Open Collector
Load
Power
Supply
dc -
common
X1
W1
PM _ C _ (C) _ - A A A A B _ _
Power Supply Note:
Switched dc and Process outputs use a common power supply with a maximum current output of 40mA. As an
example, supplied current (mA) from output 1 and 2 can be 20/20, 30/10, 30/0, 10/30, etc...
Outputs
Please note all outputs are connected exclusively to slot A. Output availability is based on the part number of
your PID Control.