QPAC User's Guide

15

Chapter 2: Install & Wire

Motherboard Connector

38mm

(1.50 in)

51mm

(2.00 in)

1
2 (+)

3 (-)

08-5286

Input Wiring

CD Control Card, Solid-
State Contactor, Contact
Closure Input.

CD Control Card — Contact Closure Input Contactor

For a contact closure input to the CD Control Card, the contact is wired to
pins 1 and 2 (+) of the input signal connector. A closed contactor input turns
the QPAC on and an open contact turns the QPAC off. The input impedance
is 10KΩ minimum.

AF, AL, BF, BV
Potentiometer Input.

Process Input - AF, AL, BF and BV Control Cards

The QPAC AF, AL, BF and BV Control Cards are defined as follows:

AF - Phase Angle Control
AL - Phase Angle Control with Current Limit
BF - Burst Firing (Zero Cross), Fixed Time Base
BV - Burst Firing (Zero Cross), Variable Time Base

All four of these cards can be wired for a manual potentiometer input or an
input from a temperature control. The following paragraphs give the connec-
tions for both configurations including an Auto/Manual configuration where
the input can be switched between manual and temperature control input.

AF, AL, BF and BV Potentiometer Input

For potentiometer input, wire a 1KΩ potentiometer to the “POT”, “+” and “-” con-
nections of the control card. The wiper of the potentiometer should be connect-
ed to the “+” connection. The control card must be converted to a voltage input
by replacing a jumper. See "Bias and Gain Adjustments," Chapter 3.

Motherboard Connector

1KΩ Pot

56 to 57mm

(2.19 to 2.75 in)

CW-

CCW+

Pot

1

5 -

+

70 to 95mm

(2.75 to 3.75 in)

requires 0 to
5VÎ (dc) input
card setting

Input Ranges

0 to 5V

Î

(dc)

1 to 5V

Î

(dc)

0 to 10V

Î

(dc)

0 to 20mA (dc)
4 to 20mA (dc)
1KΩ potentiometer