Watlow Series 101 User Manual

Series 101, User’s manual, Temperature controller

Advertising
background image

Watlow Series 101 User’s Manual

1

(2060)

Control Mode
• On-Off
• Nominal switching hysteresis:

Type J thermocouple; 1.7°C (3°F);
Type K thermocouple; 2.2°C (4°F)

Operator Interface
• 76 mm (3 in.) dial scale calibrated to compensate for sensor

non-linearities

• Dual °C and °F scales
• D-shaft pot and adjustable ratchet knob

Input
• Thermocouple with automatic cold junction compensation
• Sensor may be isolated or grounded
• Sensor break protection de-energizes output

Output
• Electromechanical relay with contact suppression, 3A, SPST: 3A

@ 230V~ 3A @ 30V

Î

(dc), 125VA pilot duty @ 120 or 230V~

• Solid-state relay, Form A, 0.5A @ 24V~ min., 230V~ max.,

opto-isolated burst fire switched, without contact suppression.
Off state output impedance is 31M

.

• Switched dc signal provides a non-isolated minimum turn on

voltage of 3V

Î

(dc) into a minimum 500W load maximum on

voltage not greater than 28V

Î

(dc) into an infinite load.

Accuracy
• Calibration accuracy and sensor conformity: ±1% of span, at 25°C

± 3°C (77°F ±5°F) ambient and rated line voltage ±1%

• Set point accuracy: ±2% of dial scale
• Accuracy span: 540°C (1000°F) minimum
• Temperature stability: 9µV/°C (5µV/°F) ambient, maximum

referred to the input

• Voltage stability: ±0.01% of span per % of rated line voltage

Agency Approvals
• CE approved:

89/336/EEC Electromagnetic Compatibility Directive

EN 55011: 1991 Emissions class B
EN 50082-1: 1992 Immunity

73/23/EEC Low Voltage Directive

EN 61010-1: 1993 Safety

873, File #E43684

to C22.2 No. 24, File #E43684

• ANSI Z21.23. Gas Appliance Thermostats

Classification
• Installation category II, Pollution category II

Terminals
• Quick connects, 1/4 in. (6 mm) appliance

Power
• 115V~, ±10%, 50/60 Hz
• 230V~, ±10%, 50/60 Hz
• 24V~, ±10%, 50/60 Hz
• 4VA power consumption

Operating Environment
• 0 to 70°C (30 to 158°F)
• 0 to 90% RH, non-condensing

Dimensions
• See page 2.

Weight
• 0.3kg (0.7 lb)

and

are registered trademarks of Underwriter’s

Laboratories, Inc.

Note: Specifications subject to change without notice.

Specifications

Series 101

User’s Manual

Temperature Controller

1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com

TOTAL

3 Year Warranty

CUSTOMER

SATISFACTION

The Watlow Series 101 is an on-off temperature

controller that comes in three common temperature
ranges or can be custom ordered to meet your require-
ments. The input sensor can be either Type J or K
thermocouple. The setpot is integral and has both degree
Celsius and Fahrenheit scales.

General Description

$5.00

Made in the U.S.A.

Printed on Recycled Paper

10% Postconsumer Waste

0600-0036-0001 Rev D
January 2001
Supersedes:
0600-0036-0001 Rev C

Advertising