Watlow Series 102 User Manual

Series 102, User’s manual, On-off temperature controller

Advertising
background image

Series 102

User’s Manual

On-off Temperature

Controller

1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com

The Watlow Series 102 is a 1/16 DIN, on-off

temperature controller with a thermocouple or RTD sensor
input.

The compact size of the controller allows more flexibility

in applications where space is a problem. The Series 102 has
a standard integral setpot and front panel LED output
status indicator.

(1915)

Control Mode
• On-off
• Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
• Sealed membrane front panel
• LED indication of output status
• Dial scale calibrated to compensate for sensor non-linearities
• Integral set point

• Dual temperature scale (°F and °C)

Input
• Thermocouple or platinum RTD available
• Thermocouple with automatic cold junction compensation
• Thermocouple may be isolated or grounded
• Thermocouple and RTD break protection de-energizes output
• 2- or 3-wire RTD input, 100

, 500

or 1000

@ 0°C calibrated for

0.003850

/

°C curve, factory selectable

Output
• Electromechanical relay, 3A, Form C, SPDT: 3A @ 240V

Å

, 3A @

28V

Î

(dc), resistive, 240V~ 275 VA pilot duty rated

• Solid-state relay, Form A, 0.5A @ 24V

Å

min., 264V

Å

max., opto-

isolated, zero cross switching

• Switched dc configuration; switched dc supply voltage 3 to 32V

Î

(dc) into a minimum 500

load

Accuracy
Adjustable Set Point
• Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)

ambient and rated line voltage ± 1%

• Set point accuracy: ±3% of dial scale
• Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
• Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C

±3°C) ambient and rated line voltage ±1%

Temperature Stability
• Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input

referenced

• RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
• ±0.01% of span (min span of 1000°F or 540°C) per % of rated line

voltage

Agency Approvals
• CE: EN61010 - Safety

EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2

873, File #E43684

to C22.2 No. 24, File #E43684

• Approved for use in commercial cooking applications

Terminals
• Screw clamp terminal: 12- to 26-gauge wire
Power
• 120V~, +10%/-15%, 50/60 Hz
• 230V~ to 240~, +10%/-15%, 50/60 Hz
• 10VA maximum power
Operating Environment
• 32 to 131°F (0 to 55°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -4 to 185°F (-20 to 85°C)

Dimensions
• Height: 2.1 in (55 mm)
• Width: 2.1 in (55 mm)
• Depth: 4.0 in (102 mm)
• Behind panel: 3.50 in (89 mm)
• Front panel: 0.5 in (13 mm)

Weight
• 0.7 lb (0.3kg)

UL® is a registered trademark of Underwriter’s Laboratories, Inc.

Note: Specifications subject to change without notice.

Specifications

General Description

$5.00 Made in the U.S.A.

Printed on Recycled Paper

10% Postconsumer Waste

0600-0004-0006 Rev C
August 2000
Supersedes: 0600-0036-0002 Rev B

Registered Company

Winona, Minnesota USA

T

T

T

TO

O

O

O

O A

A

A

AL

L

L

L

3Y

Y

Y

Y

Y

Y

Y

Y

W ranty

arran

ran

ran

W

W

S

ON

Advertising