Watlow Series 103 User Manual

Series 103, User’s manual, On/off temperature controller

Advertising
background image

1

Watlow Series 103 User’s Manual

(2001)

Control Mode
• On-off
• Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
• LED indication of output status
• Dial scale calibrated to compensate for sensor non-linearities
• Integral set point

• Dual temperature scale (°F and °C)

• Fixed set point

• Manufactured to specified value

Input
• Thermocouple or platinum RTD available
• Thermocouple with automatic cold junction compensation
• Thermocouple may be isolated or grounded
• Thermocouple and RTD break protection de-energizes output
• 2- or 3-wire RTD input, 100

, 500

or 1000

@ 0°C calibrated

for 0.003850

/

°C curve, factory selectable

Output
• Solid-state relay, Form A, 0.5A @ 24V~ min., 264V~ maximum,

opto-isolated, zero cross switching

• Switched dc signal provides a non-isolated minimum turn-on volt-

age of 3V

Î

(dc) into a minimum 500

load, maximum on voltage

not greater than 32V

Î

(dc)

• Electromechanical relay, 8A, Form C, SPDT: 8A @ 240V~ resis-

tive, 8A, 28V

Î

(dc) resistive, 275 VA pilot duty rated

Accuracy
Adjustable Set Point
• Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)

ambient and rated line voltage ± 1%

• Set point accuracy: ±3% of dial scale
• Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
• Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C

±3°C) ambient and rated line voltage ±1%

Temperature Stability
• Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input

referenced

• RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
• ±0.01% of span (min span of 1000°F or 540°C) per % of rated

line voltage

Agency Approvals
• CE: EN61010 - Safety

EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2

873, File #E43684

to C22.2 No. 24, File #E43684

• Approved for use in commercial cooking applications
Terminals
• Captive screw, cage clamp connection, 0.155 in. (4mm) max.

width screwdriver blade, 30 to 14-gauge wire

Mounting
• DIN rail, DIN EN50022, 35mm x 7.5mm
• Sub-panel mounting
Power
• 120V~, +10%/-15%, 50/60 Hz
• 230V~ to 240~, +10%/-15%, 50/60 Hz
• 10VA maximum power
Operating Environment
• 32 to 131°F (0 to 55°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -4 to 185°F (-20 to 85°C)
Dimensions
• Width: 2.28 in (60 mm)
• Height: 4.45 in (115mm)
• Depth: 3.89 in (100 mm)
Weight
• 0.7 lb. (0.3kg)

UL® is a registered trademark of Underwriter’s Laboratories, Inc.
Note: Specifications subject to change without notice.

Specifications

Series 103

User’s Manual

On/Off Temperature

Controller

1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com

TOTAL

3 Year Warranty

CUSTOMER

SATISFACTION

0600-0004-0007 Rev D
January 2001
Supersedes: 0600-0004-0007 Rev C

$5.00 Made in the U.S.A.

Printed on Recycled Paper

10% Postconsumer Waste

The Watlow Series 103 is a DIN rail mount, on-off

temperature controller with a thermocouple or RTD
sensor input. The DIN rail mounting offers quick and
easy installation with the use of simple hand tools. The
controller may also be flush mounted.

The Series 103 can be factory configured as either a

heat or cool output. Output types include electromechani-
cal relay, solid-state relay or open collector output.

The Series 103 has an LED for output status

indication and can be ordered with an integral, adjustable
set point or a fixed set point.

General Description

Advertising