Watlow’s Series 104 is an economical open board, on-off

temperature controller with a thermocouple or RTD sensor
input. Installation and setup of the control is simple and
easy.

The Series 104 offers setpot options including integral

or fixed set point. Factory selectable options include electro-
mechanical relay, SSR or switched dc output, dual scale,
and heat or cool control mode.

(1922)

Control Mode
• On-off
• Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
• LED indication of output status
• Dial scale calibrated to compensate for sensor non-linearities
• Integral set point

• Dual temperature scale (°F and °C)

• Fixed set point

• Manufactured to specified value

Input
• Thermocouple or platinum RTD available
• Thermocouple with automatic cold junction compensation
• Thermocouple may be isolated or grounded
• Thermocouple and RTD break protection de-energizes output
• 2- or 3-wire RTD input, 100

, 500

or 1000

@ 0°C calibrated for

0.003850

/

°C curve, factory selectable

Output
• Solid-state relay, Form A, 0.5A @ 24V~ min., 264V~ maximum,

opto-isolated, zero cross switching

• Switched dc signal provides a non-isolated minimum turn-on voltage

of 3V

Î

(dc) into a minimum 500

load, maximum on voltage not

greater than 32V

Î

(dc)

• Electromechanical relay, 8A, Form C, SPDT: 8A @ 240V~ resistive,

8A, 28V

Î

(dc) resistive, 240V~ 275 VA pilot duty rated

Accuracy
Adjustable Set Point
• Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)

ambient and rated line voltage ± 1%

• Set point accuracy: ±3% of dial scale
• Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
• Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C

±3°C) ambient and rated line voltage ±1%

Temperature Stability
• Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input

referenced

• RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
• ±0.01% of span (min span of 1000°F or 540°C) per % of rated line

voltage

Agency Approvals
• CE: EN61010 - Safety

EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2

873 Recognized, File #E43684

Recognized to C22.2 No. 24, File #E43684

• Approved for use in commercial cooking applications

Terminals
• Sensor input

• Screw clamp terminal: 12-26 gauge wire

• Power input and control output

• #6 screws on barrier strip

Power
• 120V~, +10%/-15%, 50/60 Hz
• 230V~ to 240~, +10%/-15%, 50/60 Hz
• 10VA maximum power
Operating Environment
• 32 to 131°F (0 to 55°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -4 to 185°F (-20 to 85°C)

Dimensions
• Width: 4.5 in (114 mm)
• Length: 4.0 in (102 mm)
• Depth: 1.5 in (38 mm)

Weight
• 0.7 lb (0.3kg)

UL® is a registered trademark of Underwriter’s Laboratories, Inc.

Note: Specifications subject to change without notice.