Restarting a program, Remote hold input, Run and halt a program – Watlow Series 1500 User Manual

Page 59: How to run a program, How to halt a program, Manual tuning

Advertising
background image

Technical Reference

Manual Tuning

For optimum control

performance, tune the

1500 to the themal system. The tuning

settings here are meant for a broad spectrum of applications; your system may have

somewhat

different requirements.

Refer to the key flow

charts,

diagrams and defini-

tions on Pages 42 - 61 for prompt location and description. Repeat this tuning

procedure for both Channel 1 and 2.

NOTE:

When tuning in

the Heat mode, use H where X appears.

When tuning In the Cool mode, use C where X appears.

1.

Apply power to the Series 1500 and enter a set point in the Change Data Mode

(CHG DATA). Next, go

into the Change Parameter Mode

(CHG PARA), and

enter (1) at

the GA parameter. Using the MODE, UP/DOWN

and ENTER keys,

set the operating parameters initially:

l

Proportional Band: 1X P b = O

l

Cycle Time:

!

1 X C T = 5

.

Reset:

l

1 X RS = 0.00

l

Dead Band: 1X d b = O

.

Rate: 1X RT = 0.00

l

Caiibration Offset: 1X CA = 0

l

Rate Band: 1X Rb = 3.00

To tune a parameter relating to heat, set the set point above ambient temperature,
for cooling, set the set point below ambient temperature. Allow actual process tern-

perature to stabilize at

or near set point.

The ACTUAL display indicates when the

load is stabilized near set point.

2.

3.

4.

5.

6.

Proportional Band Adjustment: Gradually increase Pb until the ACTUAL display

temperature stabilizes to a constant value. The temperature will not be right on

set point because the initial reset value is 0.00 repeats per minute. The ACTUAL

temperature will stabilize below the desired set point. (When Pb = 0, RS, Rb,

RT, and Ct are inoperative, and the 1500 functions as a simple ON/OFF control

with a 3°F/1.7°C switching differential.

Reset Adjustment: Gradually increase

RS

until the ACTUAL display temperature

begins to oscillate or “hunt.” Then slowly decrease RS until the ACTUAL display
stabilizes again near set point. NOTE: This is a slow procedure, taking from

minutes to hours to obtain optimum value.

Rate Adjustment: Increase RT

to

1

.OO min. Then raise set

point by 20° to 30°F/

11° to 17°C. Observe the system’s

approach to set point. lf the bad

tempera-

ture overshoots set point, increase RT to 2.00 minutes.

Cycle Time Adjustment: Set CT as required. Optimum system controls is always

achieved with faster cycle times. However, if a mechanical contactor or solenoid
is switching power to the load,

a longer cycle time may be desirable

to minimize

wear on the mechanical components. Experiment until the cycle time is consis-

tent with the quality of control you want.

Calibration Offset Adjustment: You may want your system to control to a tem-
perature other than the value

coming from the input

sensor. If so, measure the

difference (as much as ±90°F/±50°C) between that temperature, perhaps at

another point in the system, and the process value showing in the alphanumeric
display. Then enter the amount of CAL Offset

YOU want

Calibration offset adds

or subtracts degrees from the value of the input signal.

Tuning, Chapter

4

WATLOW Series 150O

User's Manual

59

Advertising