Output wiring, Solid state wiring, 0.5a, Switched dc, open collector – Watlow Series 365 User Manual
Page 8: Electromechanical relay, Solid state relay, 0.5a, Electromechanical relay, form c
Advertising

8
WATLOW Series 365 User’s Manual
Output Wiring
Solid State Relay, 0.5A
With Contact Suppression:
3 6 5 _ - B _ _ _ - _ 0 0 0
Without Contact Suppression:
3 6 5 _ - K _ _ _ - _ 0 0 0
Only available on units with ON/OFF or PI control
Figure 10 -
Solid State Relay
Wiring
External
Load
1 0
N . O .
COM
9
Fuse
L1
L2
Switched DC, Open Collector
Non-Isolated
3 6 5 _ - C _ _ _ - _ 0 0 0
Only available on units with ON/OFF or PI control
Figure 11 -
Switched DC Wiring
External
Load
1 0
9
O.C. -
O.C. +
Electromechanical Relay, Form C
With Contact Suppression
5 Amps
3 6 5 _ - D _ _ _ - _ 0 0 0
10 Amps
3 6 5 _ - E _ _ _ - _ 0 0 0
Figure 12 -
Electromechanical
Relay Wiring
External
Load
1 0
9
N . O .
COM
8
N . C .
Fuse
L1
L2
Advertising