Input ranges, Setup – Watlow Series 942 User Manual

Page 26

Advertising
background image

Setup, Chapter 4

26

WATLOW Series 942 User's Manual

Setup

dAtA

bAud

Addr

Prot

LOg

Int

tAg

PStr

Input Type

Sensor Range Low

Sensor Range High

J

32

°

F/0

°

C

1382

°

F/750

°

C

K (appears as H)

-328

°

F/-200

°

C

2282

°

F/1250

°

C

t

-328

°

F/-200

°

C

662

°

F/350

°

C

n

32

°

F/0

°

C

2282

°

F/1250

°

C

Pt2

32

°

F/0

°

C

2543

°

F/1395

°

C

c

797

°

F/425

°

C

4200

°

F/2315

°

C

r

32

°

F/0

°

C

2642

°

F/1450

°

C

S

32

°

F/0

°

C

2642

°

F/1450

°

C

b

*32

°

F/0

°

C

3092

°

F/1700

°

C

rtd (1

°

)

-328

°

F/-200

°

C

1112

°

F/600

°

C

rt.d (0.1

°

)

-99.9

°

F/-99.9

°

C

392.0

°

F/200.0

°

C

0-5 (VDC)

-5.00/-50.0/-500

35.00/350.0/3500

420 (mA)

-5.00/-50.0/-500

35.00/350.0/3500

* b t/c: Useable
range is suggested
to be 1598 to 3092

°

F

or 870 to 1700

°

C.

Range is at 32

°

to

allow using at low
temperatures
without range low
sensor errors.

NOTE:

Profile Start: Selects whether the profile starts at the current set point value or
the current process value.
Range: Proc or StPt

Range: StPt

Baud: Represents the current baud rate for serial communications. This
parameter appears if your Series 942 has communications.
Range: 300, 600, 1200, 2400, 4800, 9600

Default: 1200

Data: Allows the user to select the data bits and parity for communication.
This parameter appears if your Series 942 has communications.
Range: 7 o = 7 data bits and odd parity

Default: 7 o

7 E = 7 data bits and even parity
8 n = 8 Data bits and no parity

Protocol: Selects the communication protocol. This parameter appears if your
Series 942 has communications.
FULL = ANSI X3.28 2.2 - A.3

On = XON - XOFF

Range: FULL or On

Default: FULL

Address: Selects the address for this unit if Prot = FULL. This parameter
appears if your Series 942 has communications.
Range: 0 to 31

Default: 0

Log: Selects the data logging function for a printout of the data. This parame-
ter appears if your Series 942 has communications, and Prot = On.
Range: On or OFF

Default: OFF

Interval: Selects the time interval for the logging function This parameter
appears if your Series 942 has communications, Prot = On, and Log = On.
Range: 0.0 to 60.0 minutes

Default: 0.0

Tag: Selects what variables are to be transmitted out during the data logging
function. This parameter appears if your Series 942 has communications,
Prot = On, and Log = On.
P = Process

S = Set Point

A = Auxiliary Status

Range: PSA, PS-, P-A, P--, -SA, -S-, --A, ---

Default: ---

Table 1- Input Ranges