1 3

Attribute #

Access Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

109

Get/Set

InfoSense

TM

4

INT

Set sensor point 4 code

0 to 999

(default is 500)

110

Get/Set

Process Scale Low mA

DINT

Set the low scale for process
input

1.00 to 20.00 mA

(* 1000) (when Sensor

Type set to mA, default =
4.00 mA)

111

Get/Set

Process Scale Low Volts

DINT

Set the low scale for process
input

0.50 to 10.00 V
(* 1000)

(when Sensor Type set to
Volt, default = 1.00 V)

112

Get/Set

Process Scale High mA

DINT

Set the high scale for process
input

1.00 to 20.00 mA
(* 1000) (when Sensor
Type set to mA, default =
20.00 mA)

113

Get/Set

Process Scale High Volts

DINT

Set the high scale for process
input

0.50 to 10.00 V

(* 1000)

(when Sensor Type set to
Volt, default = 5.00 V)

114

Get/Set

Units Scale Low

DINT

Set the low range for process
input units

-1999 to 9999 (* 1000)

(default = -1999)

115

Get/Set

Units Scale High

DINT

Set the high range for
process input units

-1999 to 9999 (* 1000)

(default = 9999)

116

Get/Set

Set Point Low Limit
Thermocouple

DINT

Set the low range for the set
point

Minimum operating range
(of sensor) to Set Point
High Limit – 0.001 (if
Sensor Type =
Thermocouple, default =
min. for default sensor
(* 1000)

117

Get/Set

Set Point Low Limit RTD

DINT

Set the low range for the set
point

-328 to Set Point High
Limit – 0.001 (if Sensor
Type = RTD, default = -
328)
(* 1000)

118

Get/Set

Set Point Low Limit mA
and volts

DINT

Set the low range for the set
point

-1999 to Set Point High
Limit – 0.001 (if Sensor
Type = V or mA, default =
-1999)
(* 1000)

119

Get/Set

Set Point High Limit
Thermocouple

DINT

Set the high range for the
set point

Set point low limit to max
operating range of sensor,
if Input Type =
Thermocouple (default =
max operating range for
K-Thermocouple) (* 1000)

120

Get/Set

Set Point High Limit RTD

DINT

Set the high range for the
set point

Set Point Low Limit +
0.001 to 1472, if Input
Type = RTD (default =
1472) (* 1000)

Advertising