Power Limiting: The power limiting function in % power for heat only. Power
Limiting will function if [`pb1] is set to [```0].
Range: Dependent on output type. 0 to100

Default: 100

Display: Selects which displays are active or viewable. Five seconds after selected,
the appropriate display goes blank. Press ‰Advance, ¿Up-arrow or ¯Down-arrow
to override this feature and cause the current value to be displayed for 5 seconds.
Range: [`nor] Normal displays

Default: [`nor]

[`SEt] Set Point - lower display only
[`Pro] Process - upper display only

Setup Menu

Parameter

Value

Range

Factory Default

Appears If:

[`LOC]

**

[```0], [```1], [```2], [```3], [```4]

0

[``In]

[```J], [```H], [```t], [```n],

[```J]

DIP switch selectable.

[```S], [`rtd], [`r†d], [`0-5], [`420]

[`dEC]

0, 0.0, 0.00

0

[``In] is set to [`0-5]
or [`420]

[`C_F]

[```C] or [```F]

Dependent on [`dFL]

[``In] is set to [```J],
[```H], [```t], [```n],
[```S], [`rtd], or [`r†d]

[``rL]

[``rL] to [``rh]

Input dependent.

[``rh]

[``rh] to [``rL]

Input dependent.

[`Ot1]

[``ht] or [``CL]

[``ht]

[`HSC]

1 - 99, 0.1 - 9.9, 0.01 - 0.99°F

3, 0.3, 0.03°F

1 to 55, 0.1 to 5.5, 0.01 to 0.55°C

2, 0.2, 0.02°C

[`Ot2]

[`Con] = Control

[`Con]

[`PrA] = Process Alarm
[``Pr] = Process with no alarm message
[`dEA] = Deviation alarm
[``dE] = Deviation with no alarm message
[``no] = None

[`HSA]

1 - 9999, 0.1 - 999.9, 0.01 - 99.99°F

3, 0.3, 0.03°F

[`Ot2] is not set to [`Con]

1 - 5555, 0.1 - 555.5, 0.01 - 55.55°C

2, 0.2, 0.02°C

or [``no]

[`LAt]

[`LAt] or [`nLA]

[`nLA]

[`Ot2] is not set to [`Con]
or [``no]

[`SIL]

[``On] or [`OFF]

[`OFF]

[`Ot2] is set to [`dEA] or
[``dE]

[`rtd]

[`JIS] or [`din]

[`din]

[``In] is set to [`rtd] or
[`r†d]

[`rP`]

[`Str] is set to Ramping on power up

[`OFF]

[``on] is set to Ramping to set point always
[`OFF] is set to None

[`rt`]

0 to 9999

100°/hr

[``rP] is not set to [`OFF]

[`P`L]

0 to 100

100

[`dsP]

[`nor] = normal

[`nor]

[`SEt] = Set Point (lower only)
[`Pro] = Process (upper only)

**

LOC Functions

[```0]: All operating parameters may be viewed or changed. Manual operation is permitted. Bumpless transfer to manual

mode will occur on sensor break.

[```1]: The set point, actual, and alarm settings are only visible parameters, set point is adjustable in this level. Manual

operation and auto-tune are permitted. Bumpless transfer to manual mode will occur on sensor break.

[```2]: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual

operation is permitted. Bumpless transfer to manual mode will occur on sensor break.

[```3]: The set point and actual are the only visible parameters, set point is adjustable in this level. Manual operation is not

permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.

[```4]: The set point and actual are the only visible parameters, set point is not adjustable in this level. Manual operation is

not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.

Input Type

Sensor Range Low

Sensor Range High

[```J]

0°C/32°F

750°C/1382°F

[```H]

-200°C/-328°F

1250°C/2282°F

[```t]

-200°C/-328°F

350°C/662°F

[```n]

0°C/32°F

1250°C/2282°F

[```S]

0°C/32°F

1450°C/2642°F

[`rtd]

(1°)

-200°C/-328°F

700°C/1292°F

[`r†d] (0.1°)

-128.8°C/-199.9°F

537.7°C/999.9°F

[`420]

4mA/-999 units

20mA/9999 units

[`0-5]

0VÎ (dc)/-999 units

5VÎ (dc)/9999 units

Table 15a -
Input Ranges.

{`dSP}

Table 15b -
Setup Menu Prompts
and Descriptions.