Watlow VPAC-BT Remote Mount Transformer User Manual
Page 2

Input
Pot (+) (-)
T
ransformer Plug
R22
Zero Cross
SSR
- +
BT
8
7
6
5
4
3
2
1
4
3
2
1
Heater
Safety Contactor
if required
Semiconductor
Fuse
Branch Circuit
Fuses
T
ransformer
Fuses
Primary
T
ransformer
Connections
(bottom view)
red
black
white
black
240
V
olt
120
V
olt
Secondary
T
ransformer
Connections
(top view)
Note:
Input is 250 ohms.
For 5K input, cut R22.
Common
Positive
Pot (+) (-)
Manual Control
L1
L2
12V~(ac)
Common
(center tap)
12V~(ac)
orange
white
violet
Note:
The controls transformer must
be on the same phase as the
load. See wiring diagram.
All
hot lines to the transformer
should be fused at 1 amp with
the proper line voltage.
For manual control, a 1K
Ω
potentiometer may be connected
to the
A
T
card input terminals.
W
a
tlow offers a Manual Control
Kit, P/N 08-5362. Using this
potentiometer requires removing
the 5K
Ω
, R2 resistor for higher
impedance.
Bias and gain adjustment is
required when changing from 4-
20mA
input to a manual control
input or a voltage input.
W
iring Diagram for VP
AC-BT
Remote Mount T
ransformer