ATEX Certification

(1) Technical Data

a. ATEX Intrinsically Safe Type
Caution for ATEX Intrinsically safe type.
Note 1. EJX series pressure transmitters with

optional code /KS25 for potentially

explosive atmospheres:

• No. KEMA 04ATEX1116 X

• Applicable Standard: EN 50014, EN 50020,

EN 50284, EN50281-1-1

Note 2. Ratings

[EEx ia IIC T4]

Type of Protection and Marking Code:

EEx ia IIC T4

Group: II

Category: 1GD

Ambient Temperature: –40* to 60°C

* –15°C when /HE is specified.

Maximum Process Temperature (Tp.): 120°C

Maximum Surface Temperature for dust proof.

T85°C (Tamb.: –40* to 60°C, Tp.: 80°C)

T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)

T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)

* –15°C when /HE is specified.

Degree of Protection of the Enclosure:

IP66 and IP67

Electrical Data

• When combined with Trapezoidal and

Rectangular output characteristic FISCO

model IIC barrier

Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,

Ci = 1.76 nF, Li = 0 µH

• When combined with Linear characteristic

barrier

Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,

Ci = 1.76 nF, Li = 0 µH

[EEx ia IIB T4]

Type of Protection and Marking Code:

EEx ia IIB T4

Group: II

Category: 1GD

Ambient Temperature: –40* to 60°C

* –15°C when /HE is specified.

Maximum Process Temperature (Tp.): 120°C

Maximum Surface Temperature for dust proof.

T85°C (Tamb.: –40* to 60°C, Tp.: 80°C)

T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)

T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)

* –15°C when /HE is specified.

Degree of Protection of the Enclosure:

IP66 and IP67 Electrical Data

• When combined with Trapezoidal or

Rectangular output characteristic FISCO

model IIB barrier

Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,

Ci = 1.76 nF, Li = 0 µH

Note 3. Installation

• All wiring shall comply with local installation

requirements. (Refer to the installation

diagram)

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void KEMA

Intrinsically safe Certification.

Note 5. Special Conditions for Safe Use

• In the case where the enclosure of the

Pressure Transmitter is made of aluminium,

if it is mounted in an area where the use of

category 1 G apparatus is required, it must

be installed such, that even in the event of

rare incidents, ignition sources due to impact

and friction sparks are excluded.

Note 6. Installation instructions

• From the safety point of view the circuit shall

be considered to be connected to earth.

As this deviates from the FISCO system

in acordance with IEC TS 60079-27 care

has to be taken that the (local) installation

requirements are taken into account as well.

When used in a potentially explosive

atmosphere, requiring the use of apparatus

of equipment category 1D or 2D, certified

cable entry devices shall be used that are

suitable for the application and correctly

installed.

FISCO Model

Non-Hazardous

Locations

Hazardous Locations

F0207r.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit and

Safety Barrier

(FISCO Model)

Terminator

Data

U

U

I

I.S. fieldbus system complying with FISCO

Advertising