Yokogawa EJX115A User Manual

Page 3

Advertising
background image

The criterion for such interconnection is that the

voltage (Ui), the current (Ii) and the power (Pi),

which intrinsically safe apparatus can receive,

must be equal or greater than the voltage (Uo),

the current (Io) and the power (Po) which can be

provided by the associated apparatus (supply unit).

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected

to the fieldbus line must be equal or less than 5 nF

and 10 µH respectively.

Ci ≤ 5 nF, Li ≤ 10 µH

Supply unit
The supply unit must be certified by a Notified

body as FISCO model and following trapezoidal or

rectangular output characteristic is used.

Uo = 14...17.5 V (I.S. maximum value)
Io based on spark test result or other

assessment, No specification of Lo and Co is

required on the certificate or label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

Loop resistance Rc: 15...150 Ω/km

Inductance per unit length Lc: 0.4...1 mH/km

Capacitance per unit length Cc: 80...200 nF/km

Length of spur cable: max. 30 m (IIC and IIB)

Length of trunk cable: max. 1 km (IIC) or 5 km

(IIB)

Terminators
The terminator must be certified by a Notified body

as FISCO model and at each end of the trunk

cable an approved line terminator with the following

parameters is suitable:

R = 90 . . . 102 Ω

C = 0 . . . 2.2 µF. (0.8...1.2 µF is required in

operation)

The resistor must be infallible according to IEC

60079-11.

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

Entity Model

Non-Hazardous

Locations

Hazardous Locations

F0208.ai

Terminator

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit and

Safety Barrier

Terminator

Data

U

U

I

I.S. fieldbus system complying with Entity model

I.S. values Power supply-field device:

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

Calculation of max. allowed cable length:

Ccable ≤ Co - ∑Ci - ∑Ci (Terminator)

Lcable ≤ Lo - ∑Li

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.
b. ATEX Intrinsically Safe Type (for EJX90A)

Caution for ATEX Intrinsically safe type.

Note 1. EJX multivariable transmitter with optional

code /KS25 for potentially explosive

atmospheres:

• No. KEMA 06ATEX0278 X

• Applicable Standard: EN 60079-0:2006,

EN 50020:2002, EN 60079-27:2006,

EN 50284:1999, EN 50281-1-1:1998

Note 2. Ratings

[Ex ia IIC T4]

Type of Protection and Marking Code:

Ex ia IIC T4

Group: II

Category: 1GD

Ambient Temperature: –40 to 60ºC

Maximum Process Temperature (Tp.): 120ºC

Maximum Surface Temperature for dust-proof.

T85ºC (Tamb.: –40* to 60ºC, Tp.: 80ºC)

T100ºC (Tamb.: –40* to 60ºC, Tp.: 100ºC)

T120ºC (Tamb.: –40* to 60ºC, Tp.: 120ºC)

* –15ºC when /HE is specified.

Degree of Protection of the Enclosure:

IP66 / IP67

Advertising