<3. Parameter Setting>

3-13

IM 01C25T01-06EN

3.2.3 Range Change

The range values are factory-set as specified by

the customer. To change the range, follow the steps

below.
(1) Keypad input — LRV and URV
The measurement span is determined by the upper

and lower range values. In this method, the upper

and lower range values can be set independently,

and the span changes according to the range limit

values sent to the transmitter.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

Re-range → Keypad input

EJX_HART 5[1.2]

DTM

Easy Setup → or Configuration →

Analog Output →

→ LRV

Lower range value

→ URV

Upper range value

NOTE

The calibration range can be set as LRV > URV

under the following conditions, reversing the 4

to 20 mA output signal. When using the integral

indicator, change the user set scale values

accordingly.

Conditions:

LSL ≤ LRV ≤ USL

LSL ≤ URV ≤ USL

|URV – LRV| ≥ Min Span

LSL: Lower sensor limit of range setting

USL: Upper sensor limit of range setting

(2) Apply values — changing the ranges while

applying an actual Input

This feature allows the lower and upper range

values to be setup automatically with the actual

input applied. If the upper and lower range values

are set, URV and LRV are changed at the same

time.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

Re-range → Apply values →

EJX_HART 5[1.2]

DTM

Configuration → Analog Output →

Apply values →

The measurement span is determined by the upper

and lower range values. Changing the lower range

value causes the upper range value to change

automatically, keeping the span constant. If a

change in the lower range value causes the upper

range value to exceed the measuring limit of the

transmitter, an error message appears and the

transmitter holds the output signal right before the

error occurred. Enter the correct values within the

range of the sensor limits.

Note that changing the upper range value does

not cause the lower range value to change. Thus,

changing the upper range value also changes the

span.

3.2.4 Output Mode

The mode setting for the output signal and the

integral indicator can be performed independently.
The output mode for the output signal is set as

specified in the order when the instrument is

shipped. Follow the procedure below to change the

mode.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

EJX_HART 5[1.2]

DTM

Easy Setup → or Configuration →

Analog Output →

→ Xfer fnctn

Select “Linear” or “Sq root”

3.2.5 Damping Time Constant Setup

The damping time constant is set as specified in

the order when the instrument is shipped. Follow

the procedure below to change the damping

time constant. The damping time constant for the

amplifier assembly can be set here. The damping

time constant for the entire transmitter is the sum

of the values for the amplifier assembly and the

capsule assembly.
Any number from 0.00 to 100.00 can be set for the

damping time constant. Note that setting the quick

response parameter ON enables you to set the time

constant between 0.00 and 0.49 seconds.

• Procedure to call up the

Pres Damp display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

Pres Damp

EJX_HART 5[1.2]

DTM

Easy Setup → Pres Damp or

Configuration → Analog Output →

Pres Damp