IM 12B6J3-04E-E

12

FM

Certificate no.

: 3046277

IS, Class I Div. 1, GP A, B, C, D T3…T6

Electrical data

: For sensor input circuits (by connector), connected to a

FM approved intrinsically safe apparatus meeting the entity
parameters of the SENCOM sensor:
Ui = 6.1 V; Ii = 230 mA; Pi = 1.2 W; Li = 4 µH; Ci = 30 µF
or
FM approved intrinsically safe Yokogawa transmitter Model
FLXA21 series.

Ambient temperature: T6 for Tamb. -40 °C to +60 °C

T5 for Tamb. -40 °C to +75 °C
T4 for Tamb. -40 °C to +85 °C
T3 for Tamb. -40 °C to +85 °C

Note: Intrinsically safe when connected as per Control Drawing FF1-K1226QS (see Fig 3)

Control Drawing FM

The FU20F SENCOM

TM

sensor shall be

installed to a FM approved intrinsically safe
apparatus meeting the entity parameters
of the sensor as shown in the table as
maximum values, or to a FM certified
intrinsically safe Yokogawa transmitter
Model FLXA21 series.

When installing this equipment, follow the
manufacturer’s control drawing. Installation
should be in accordance with ANSI/ISA
RP 12.06.01 “Installation of Intrinsically
Safe Systems for Hazardous (Classified)
Locations” and the National Electrical Code
(ANSI/NFPA 70).

To prevent ignition of
flammable or combustible
atmospheres, disconnect
power before servicing or
read, understand and adhere
to the manufacturer’s live
maintenance procedures.

81 82 83 84 85 86 87

+ - G

Hazardous

location

Transmitter

IS CL1, DIV1, GP ABCD T3/T4/T5/T6

Tamb 85°C / 85ºC / 75ºC / 60ºc

WU11 cable

terminals 82-84,

86-87.

Maximum cable

length: 100 m.

Cable diameter:

5.8mm

Maximum values:

Ui = 6.1 V

Ii = 230 mA

Pi = 1.2 W

Li = 4 µH

Ci = 30 µF

Fig 3: FF1-K1226QS Control Drawing FM

FU20F
Model:

NPT

Dome shape

FSM

Flat surface