3. INSTALLATION OF VJCE

The VJCE can be installed horizontally on 19 inches rack complies with JIS/EIA standards, or horizontally on the

wall. Under the conditions mentioned in Article 3.2, a maximum of 5 mounting bases can be installed on one side of

the cabinet.

3.1

Environmental Conditions

3.1.1 Ambient temperature and humidity

Ambient temperature and humidity during operation of the instruments would be as follows:

Temperature: 0 to 50

°

C, Humidity: 5 to 90% RH

3.1.2 Vibration condition

Vibration of installation place would be less than 2m/s

2

at 10 to 150Hz

3.1.3 Air purification degree

Air dirty is desirous to be less than 0.2mg/m

3

. Also, corrosive gas such as hydrogen sulfide, sulfurous acid gas, chlo-

rine and conductive dust such as iron and carbon are desirous to be as little as possible.

(Note)

Permissible limit of hydrogen sulfide (H

2

S) and sulfurous acid gas (SO

2

) would be as standard of JEIDA-29 (1979) CLASS S1*.

JEIDA:

Japan Electronic Industrial Development Association JEIDA-29 (1979) CLASS S1

H

2

S: 0.01ppm or less, SO

2

: 0.05ppm or less (Ambient temperature: 25

°

C

±

5

°

C, ambient humidity: 40 to 80%RH)

3.2

Condition of Installation

NOTE

(1) Secure space for top and bottom to avoid heating.

Apart more than 100 mm from the floor board.

Apart more than 100 mm from panel top
and make air exhaust hole or set cooling
fan at panel upper.

If wall stands at back in case of rack
mounting, apart more than 60mm from the
wall for ventilation.

(2) Take enough space for front and side faces so as

not to interfere wiring, piping and maintenance area.

(3) In case storing in cabinet, air cooling is

compulsorily required to prevent from raise of
temperature.

(4) Do not install it on the heating materials.
(5) In case of installing the VJCE one above

another to up and down direction, take
installation space as shown in the figure on the
right. (78 mm for rack mounting, 128 mm for
wall mounting)

3.3

Installation

3.3.1

Installation of VJCE

Use four (4) M5 screws for installation.

3.3.2

Installation of signal conditioners

Connect the pin on the back of the signal conditioner to the VJCE connector

as shown in the figure on the right. Then tighten the fixing screw on the front

of the signal conditioner.

NOTE

Insert and pull out the signal conditioner vertically to VJCE.
Inserting and pulling it out slantwise may make the pin bent and
cause a failure such as a bad contact.

Cooling fan or exhaust hole

Cooling fan or

exhaust hole

19 inches Rack Mounting

Wall Mounting

Unit : mm

100 or more

78 or more

60 or more

100 or more

128 or more

Signal Conditioner

Fixing screw

VJCE

Blank Plate (Option)
Parts Number : T9093TT