Mounting method, Installation location, External wiring – Yokogawa JUXTA VJP1 User Manual

Page 2: 1 wall mounting, 2 din rail mounting, 3 mounting using, 4 using a duct, Warning

Advertising
background image

2

IM 77J01P01-01EN

1st Edition

1. MOUNTING METHOD

Note

Insert/pull out the main unit into/from the socket

vertically to the face of socket. Otherwise the terminals

are bent and it may cause a bad contact.

1.1 Wall Mounting

Loosen the main unit-fixing screw of the product and pull out the

main unit from the socket. Fix the socket on the wall with screws.

Next, insert the main unit into the socket and fasten the main unit

with the main unit-fixing screw.

29.5 or more

22±0.2 2-M4 or

2-ø4.5 or more

Mounting Dimensions

59±0.3

Unit: mm

Main unit-fixing

screw

Socket

Main unit

Threaded hole for

fixing the main unit

Mounting

screws

1.2 DIN Rail Mounting

Insert a DIN rail into the upper part of the DIN rail groove on the

rear of the socket, and then slide the slide lock at the lower part of

the socket upwards until the socket is fixed into position as shown

below

DIN rail

DIN rail

(Rear of socket)

Slide look

DIN rail

Fit into here

Push

1.3 Mounting Using

When using a multi-mounting base, see the User's Manual for

VJCE (VJCE Mounting Base).

1.4 Using a Duct

When using a wiring duct, install the duct at least 30 mm away

from the top and bottom faces of the main unit.

2. INSTALLATION LOCATION

• Avoid the following environments for installation locations:

Areas with vibration, corrosive gases, dust, water, oil, solvents,

direct sunlight, radiation, a strong electric field, and/or a strong

magnetic field, altitude of more than 2000m above sea level.

• If there is any risk of a surge being induced into the power

line and/or signal lines due to lightning or other factors, a

dedicated lightning arrester should be used as protection for

both this converter and a field-installed device.

• Operating temperature/humidity range: 0 to 50 C/5 to 90%RH

(no condensation)

3. EXTERNAL WIRING

WARNING

Be sure to turn OFF the power supply before wiring to

avoid the risk of electric shock. Use a tester or similar

device to ensure that no power is being supplied to a

cable to be connected.

Note

When power of VJP1 is turned on/off, one pulse may be

counted by the pulse input device which connects to the VJP1.

Wiring should be connected to the terminals on the socket

of the product. The terminals for external connections are of

M3 screws. Use crimp-on terminal lugs for connections to the

terminals.

• Recommended cables: A nominal cross-sectional area of

0.5 mm

2

or thicker for signal cables, and that of 1.25 mm

2

or

thicker for power cables.

10

11

3 2 1

4

5

6

7

8

9

Power supply

11

10

8

L+ N– GND

1

3

4

1

3

3

4

+

Input

Transmitter

Transmitter

PS+

+

PS+

+

Transmitter

5

2

Pulse output

Output-2

+

9

7

Pulse output

Output-1

When receiving voltage

pulse by running a

transmiter on an

internal power supply

When receiving current

pulse by running a

transmiter on an

internal power supply

When receiving

non-voltage contact

signal or voltage pulse

Note

Do not use output-2 for the single-output type.

The power line and input/output signal lines should

be installed away from noise-generating sources.

Other wise accuracy cannot be guaranteed.

The grounding resistance must be 100 Ω (JIS

Class D grounding). The length and thickness of

the grounding cable should be as short and thick

as possible. Directly connect the lead from the

ground terminal (terminal no. 8) of the product to the

ground. Do not carry out daisy-chained inter-ground

terminal wiring

Use of the product ignoring the specifications may

cause overheating or damage. Before turning on the

power, ensure the following:

Power supply voltage and input signal value applied to

the product should meet the required specifications.

The external wiring to the terminals and wiring to ground

are as specifications.

Do not operate the product in the presence of

flammable or explosive gases or vapors. To do so is

highly dangerous.

The product is sensitive to static electricity;

exercise care in operating it. Before you operate

the product, touch a nearby metal part to discharge

static electricity.

For 15-30 V DC (±20%) power supply, as a safety

measure, always install a circuit breaker (an IEC

60947-compatible product, 1 A, 30 V DC) in an easily

accessible location near the instrument. Moreover,

provide indication that the switch is a device for

turning off the power to the instrument.