Description of front panel, Power supply and isolaion, 1 operation indicating lamp – Yokogawa JUXTA MS5D User Manual

Page 3: 2 connector for communication, 3 selection switch and adjustment switch

Advertising
background image

3

IM 77J04S05-02E

1st Edition

Jul 29, 2005-00

Power Supply and Isolaion

Power supply rated voltage:

15-40 V DC or 100-240 V AC/DC 50/60 Hz

Power supply input voltage:

15-40 V DC (

±

20%) or 100-240 V AC/DC (

15,

+

20%) 50/60

Hz

Power consumption:

24 V DC 2.3 W, 110 V DC 2.2 W
100 V AC 4.6 VA, 200 V AC 6.4 VA

Insulation resistance:

100 M

at 500 V DC between input, output, power supply, and

grounding terminals mutually.

Withstand voltage:

2000 V AC for 1 minute between input, output, power supply and
grounding terminals mutually.
1000 V AC for 1 minute between output-1 and output-2 terminals.

4. DESCRIPTION OF FRONT PANEL

The figure below shows the converter of which the front panel cover is
open.

Connector for
communication

Selection
switch

Adjustment
switch

Operation indicating lamp:
Turns on at power on.

4.1 Operation Indicating Lamp

The operation indicating lamp shows the operation status, abnormali-
ties in a setting, and adjustment operation status by the adjustment
switch on the front panel.

(1) When the lamp is lit:

Power is turned on and the converter is in the normal status pro-
vided that the selection switch is set to the position “0.”

(2) When the lamp is blinking rapidly:

The lamp repeats the rapid blinking until the internal processing is
completed during output adjustment and the input range setting
by the adjustment switch.

(3) When the lamp is blinking slowly:

The lamp repeats the slow blinking until the converter regains its
normal status when the following abnormalities occur.
• Abnormalities in a parameter setting
• The selection switch is set to the positions other than “0.”

Input is outside of the range of

10 to 110%.

4.2 Connector for Communication

Use the connector for communication when setting the parameters us-
ing a PC (VJ77 Parameter Setting Tool) or the Handy Terminal.

< How to connect with the setting tool>

PC which is installed
with the VJ77.

*: Use the VJ77 of version R1.04 or later.

JHT200
Handy Terminal

JUXTA communication cable with
5-pin connector (F9182EE)
[Provided with VJ77 and JHT200]

Modular jack conversion
adapter (E9786WH)
[Provided with VJ77]

Dedicated adapter (E9789HA)
[Provided with VJ77]

Dedicated cable (E9786WK)
[Provided with VJ77]

4.3 Selection Switch and Adjustment Switch

The following adjustments can be performed using the switches on the
front panel (selection switch and adjustment switch) without the dedi-
cated setting tool (refer to “4.2 Connector for Communication”).
The adjusted value is saved about 1 second after operating the adjust-
ment switch. Also when the rotation direction of the adjustment switch
is changed, the adjusted value becomes effective about 1 second after
the change.

Position of selection switch

0
1
2
3
4
5
6

Rotation direction of adjustment switch

Clockwise

Counterclockwise

Item to be adjusted

No function
Output-1 zero adjustment
Output-1 span adjustment
Output-2 zero adjustment
Output-2 span adjustment
Input low range setting
Input high range setting

Adjustment operation

Increase of output adjusted value and
setting of input low/high range
Decrease of output adjusted value and
reset of input set value

[Adjusted volume by the adjustment switch]
One click changes about 0.005% of output range.

4.3.1 Adjusting Output Using the Switches on the Front

Panel

(1) Output-1 zero adjustment

Apply the 0% input signal. Turn the selection switch to “1.” Then
turn the adjustment switch clockwise to increase the output, or
turn it counterclockwise to decrease the output.

(2) Output-1 span adjustment

Apply the 100% input signal. Turn the selection switch to “2.”
Then turn the adjustment switch clockwise to increase the output,
or turn it counterclockwise to decrease the output.

Output-2 can be adjusted by the same operation as the above.

(3) Output-2 zero adjustment

Apply the 0% input signl. Turn the selection switch to “3.” Use the
adjustment switch for adjustment.

(4) Output-2 span adjustment

Apply the 100% input signal. Turn the selection switch to “4.” Use
the adjustment switch for adjustment.

4.3.2 Setting Inpt Range Using the Switches on the Front Panel

NOTE

Set the burnout action before setting the input range.
Changing the burnout action setting resets the input
range.

Turn the adjustment switch counterclockwise to reset
the set value before setting the input range.

(1) Resetting the input range

Turn the selection switch to “5” or “6”, and turn the adjustment
switch counterclockwise. Then the input low range or input high
range are reset.

(2) Setting the input low range

Apply the stable signal equivalent to 0% input from the connected
potentiometer. Turn the selection switch to “5”, and turn the ad-
justment switch clockwise. Then the input low range is set after
one second automatically.

(3) Setting the input high range

Apply the stable signal equivalent to 100% input from the con-
nected potentiometer. Turn the selection switch to “6”, and turn
the adjustment switch clockwise. Then the input high range is set
after one second automatically.

NOTE

Be sure to set the selection switch back to the position
“0” after each adjustment. Otherwise it may cause an
incorrect operation or malfunction because the
positions other than “0” are adjustment modes.

When the selection switch is set to the positions other
than “0”, the setting tool can not be used for the setting.

Advertising