5. SETTING PARAMETERS

Set the parameters using a PC (VJ77 Parameter Setting Tool) or the
Handy Terminal. Refer to “6. List of Parameters” in this manual and the
User’s Manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM
JF81-02E). Parameters are indicated inside the [ ].

5.1

Setting Burnout Action

Set the burnout action in [D43:BURN OUT].
Set “OFF”, “UP”, or “DOWN”.

NOTE

Set the burnout action before setting the input range.
Changing the burnout action setting resets the input
range.

Turn the adjustment switch counterclockwise to reset
the set value before setting the input range.

5.2

Setting Input Range

Set the input low range in [P16:IN1 LOW RNG], and input high range in
[P17:IN1 HIGH RNG].

(1) Resetting the input range

Select and set “RESET” in [P16:IN1 LOW RNG] or [P17:IN1 HIGH
RNG]. Then the input low range or input high range are reset.

(2) Setting the input low range

Apply the stable signal equivalent to 0% input from the connected
potentiometer. Select and set “EXECUTE” in [P16:IN1 LOW
RNG]. Then the input low range is set automatically.

(3) Setting the input high range

Apply the stable signal equivalent to 100% input from the con-
nected potentiometer. Select and set “EXECUTE” in [P17:IN1
HIGH RNG]. Then the input high range is set automatically.

5.3

Setting Output-1 Range

Set the output-1 range 0% in [D38:OUT1L_RNG], and the output-1
range 100% in [D39:OUT1H_RNG].

NOTE

Changing the output-1 range resets the adjusted value.

6.

LIST OF PARAMETERS

A

A07

A08

A54

A56

A58

A60

B

B07

B08

B60

D

D01

D02

D03

D04

D38

D39

D40

D41

D43

D49

D50

D60

P

P16

P17

P26

P27

P28

P29

P60

Q

Q03

Q04

Q60

MODEL

TAG NO

SELF CHK

DISPLAY1

OUTPUT1

OUTPUT2

STATUS

REV NO

MENU REV

SELF CHK

DISPLAY2

OUTPUT1

OUTPUT2

SELF CHK

SET (I/O)

TAG NO.1

TAG NO.2

COMMENT1

COMMENT2

OUT1 L_RNG

OUT1 H_RNG

OUT2 L_RNG

OUT2 H_RNG

BURN OUT

OUT1 DR

OUT2 DR

SELF CHK

ADJUST

IN1 LOW RNG

IN1 HIGH RNG

OUT1ZERO ADJ

OUT1SPAN ADJ

OUT2ZERO ADJ

OUT2SPAN ADJ

SELF CHK

TEST

OUT1 TEST

OUT2 TEST

SELF CHK

Model

Tag number

Self-check result

Display1

Output-1

Output-2

Status *

1

REV No.

MENU REV

Self-check result

Display2

Output-1

Output-2

Self-check result

Setting (I/O)

Tag number-1

Tag number-2

Comment-1

Comment-2

Output-1 low range

Output-1 high range

Output-2 low range

*2

Output-2 high range

*2

Burnout

Direction of output-1 action

Direction of output-2 action

Self-check result

Adjustment

Setting of input-1 low range

Setting of input-1 high range

Output-1 zero adjustment

Output-1 span adjustment

Output-2 zero adjustment

Output-2 span adjustment

Self-check result

Test

Forced output-1

Forced output-2

Self-check result

Parameter Display

Item

*1 The displayed status is to let the service staff know the past records of the

product.

*2 The parameters are the items to be set at the factory.