Mounting method, Installation location, 1 installing/uninstalling the mounting block – Yokogawa JUXTA FA4V Distributor (Non-isolated) User Manual

Page 2: 2 rack mounting, 3 wall mounting, 4 din rail mounting, 5 mounting dimensions

Advertising
background image

2

IM 77J08A04-01E 1st Edition

Nov, 18. 2011-00

1. MOUNTING METHOD

1.1 Installing/Uninstalling the Mounting Block

The mounting block is necessary for rack mounting or wall

mounting.
Installing the mounting block

Fit the mounting block into the grooves of the converter, and

slide it in the direction of an arrow as shown below-left.

Uninstalling the mounting block

Lift the stopper using a slotted screw-driver as shown below-

right, and pull the mounting block to remove it.

Groove

(Rack mounting)

Groove (Wall mounting)

Stopper

Mounting block

1.2 Rack Mounting

Take the FRK panel and install it on a mounting angle as shown

below. This method is suitable for high density mounting of the

converters on a 19-inch rack panel.

Mounting angle

Mounting angle

Mounting Dimensions

450±1

465±1

M5 screw

(4 places)

Supplied spacer(50) or Wiring space(30 to 60)

FRK panel

Mounting screw (M4x0.7)

(2 screws in the package)

50
25

25
50

Unit: mm

1.3 Wall Mounting

Mount the converter onto the FRK panel as shown below or

mount it directly on the wall.

FRK panel

1.4 DIN Rail Mounting

Place the converter so that the DIN rail fits into the upper part of

the DIN-rail groove at the rear of the converter, and push until it

clicks. The converter is fixed by a slide lock (at the lower part on

the rear side of the converter).
To remove the converter, pull down the slide lock using a slotted
screw-driver.

Slide lock

DIN rail

DIN rail groove

1.5 Mounting Dimensions

Mounting angle

M4×0.7 Mounting screw

Support

24.5

24.5

24.5 24.5 24.5

Angle Mounting Dimensions

n×24.5+2

M4×0.7 Mounting screw

Unit: mm

73 90

24.5

24.5

24.5

24.5 24.5

Wall Mounting Dimensions

90

2. INSTALLATION LOCATION

• Avoid the following environments for installation locations:

Areas with vibration, corrosive gases, dust, water, oil, solvents,

direct sunlight, radiation, a strong electric field, and/or a strong

magnetic field, altitude of more than 2000m above sea level.

• If there is any risk of a surge being induced into the power

line and/or signal lines due to lightning or other factors, a

dedicated lightning arrester should be used as protection for

both this converter and a field-installed device.

• Operating temperature/humidity range: 0 to 50ºC/5 to 90%RH

(no condensation)