List of parameters, Maintenance,  calibration apparatus – Yokogawa JUXTA FR5V RTD Converter (Free Range Type) User Manual

Page 4: 2 calibration procedure

Advertising
background image

4

IM 77J08R05-01E 1st Edition

2007.01.15-00

5. LIST OF PARAMETERS

Parameter Display

Items

A

DISPLAY

Display

A01

INPUT

Input value

A02

OUTPUT

Output value

A03

STATUS

Status (*1)

A04

REV NO

Revision number

B

SET

Setting

B01

TAG NO.1

Tag number 1

B02

TAG NO.2

Tag number 2

B03

COMMENT1

Comment 1

B04

COMMENT2

Comment 2

B05

TYPE

Input type

B09

UNIT

Unit

B10

ZERO

Zero (0% of input range)

B11

SPAN

Span (Input span)

B12

BURN OUT

Burnout

C

ADJUST

Adjustment

C01 OUT 0%

Output 0% adjustment

C02 OUT 100%

Output 100% adjustment

C04 ZERO ADJ

Input zero adjustment

C05 SPAN ADJ

Input span adjustment

*1: This “STATUS” is for the customer’s engineer to check the history.

6. MAINTENANCE

The product starts running immediately when the power is turned
on; however, it needs 10 to 15 minutes of warm-up before it
meets the specified performance.

6. Calibration Apparatus

A 6-dial variable resistor (Yokogawa Meters & Instruments
Corporation 279301 or equivalent)
A digital multimeter (Yokogawa 7561 or equivalent)
A precision resistor of 250 Ω ±0.01%, 1W
A setting tool for adjustment (Refer to "4. Setting Parameters"
in this manual.

6.2 Calibration Procedure

1. Connect the instruments as shown below.

1

2

3

4

5

6

7

3
2

6
7

4
5

1

A

B

B

6-dial
variable resistor

Setting tool

Output

Input

24V DC

Ro

Ro: 250Ω precision resistor for

current output

DMM

Power Supply

2 Use the 6-dial variable resistor and apply the resistance

equivalent to 0, 25, 50, 75, and 100% of the measuring range
to the converter.

3. Verify that the corresponding output voltages are 0, 25, 50, 75,

and 100% respectively and within the specified accuracy rating.
(R

o

is used for current output.)

Use the setting tool (VJ77 Parameter Setting Tool or JHT200
Handy Terminal) to adjust the input/output signals.



Input Adjustment Procedure

(1)

Input the value equivalent to 0% value of the input range
to the converter.

(2)

Read the parameter

[C04: ZERO ADJ] and check the

input value.

(3)

Select “INC” or “DEC” in the parameter

[C04: ZERO

ADJ] to adjust.

INC: Increase (Adjusts the increased value of the input
[resistance] value)

DEC: Decrease (Adjusts the decreased value of the
input [resistance] value)

RST: Reset of the adjustment value

(4)

Input the value equivalent to 100% value of the input
range to the converter.

(5)

Read the parameter

[C05: SPAN ADJ] and check the

input value.

(6)

Adjust the span in the same way as (3).

Output Adjustment Procedure

When adjusting 0% value of output:
(1) Set the adjustment value 0% in the parameter

[C0:

OUT 0%].

•The value equivalent to 0% of the output range will be
output, irrespective of the input.

(2) Check the output value via digital multimeter, and adjust

it in the parameter

[C0: OUT 0%].

•If it slips out to the (+) side, set (−) value equivalent
to slipout; if it slips out to the (−) side, set (+) value
equivalent to slipout for adjusting the output value to
0%.

*: The 100% value of output can be adjusted by the
same operation as the above in [C02:OUT100%]

For adjustment using a setting tool, refer to the User’s Manual for
each setting tool and “5. List of Parameters” in this manual.
User’s Manual for VJ77 [Document No.: IM 77J01J77-01E];

however, use the VJ77 of version R1.05 or later.

User’s Manual for JHT200 [Document No.: IM JF81-02E]