SPECIFICATION

FOR

OPEN COIL HEATERS

Long Form

Supply where indicated in these specifications, or where shown on drawings, CSA (NRTL/C) approved open
coil duct heaters as manufactured by THERMOLEC.

1- CONSTRUCTION:

• Frame shall be corrosion-resistant and made of galvanized steel of suitable gauge as required by CSA.
• Coils shall be made of high grade Nickel-Chrome alloy and shall be insulated by floating ceramic bushings from the

galvanized steel frame.

• Coil terminal pins shall be in stainless steel, mechanically secured and insulated from the frame by means of

non-rotating ceramic bushing.

• Coil support bushing shall be made of ceramic and shall be held in the frame by a lock which will keep it floating and

stress-free.

2- SAFETY CONTROLS:

• Heaters shall be equipped with fail-safe automatic reset disc-type thermal cut-out(s) located in the top frame

component above the heating elements.

• In addition to the automatic reset cut-out, heaters of 30KW and less, rated for voltages below 300 volts shall be

equipped with a fail-safe manual reset disc-type thermal cut-out, semi-recessed in the terminal box, facing the
heating element hairpin as required by CSA.

• The sensing element of the cut-out shall be stream mounted, shall be shielded from mechanical damage and shall

face the center portion of the heating section so as to make the heater non-sensitive to air flow direction.

• Cut-outs shall de-energize the heater in case of insufficient air flow.
• For maintenance and safety purposes, the heater shall be equipped with a built-in disconnect to switch the power

off at the heater location (option X1) and protective screens on both sides (option MS).

• Load fuses shall be supplied as recommended by NEC (National Electrical Code).
• When heaters are used in VAV systems, they should be modulating type “THERMO-V” equipped with an electronic

air flow sensor as described in item #8.

3- AIR FLOW:

• Duct heaters shall be non-sensitive to air flow direction and interchangeable for horizontal or vertical ducts without

impairing safety.

• Heaters shall be CSA approved for zero clearance in horizontal ducts.

4- MOUNTING METHOD:

• Heaters shall be open coil model SC slip-in type or model FC flanged type, as shown on the plans or on the coil

schedule.

• Slip-in heaters shall be suitable for insertion into the duct through an opening on its side and shall have a flange for

securing it to the duct side.

• Flanged heaters shall be suitable for attaching to matching flanges on the duct.
• Mounting flanges on both models shall be independent of the terminal box so as to allow installation without opening

the box or drilling into it.

5- SIZE & CAPACITY:

• Heater size, volts, phases, kilowatt and number of control stages shall be as per heater schedule.

6- INTERNAL WIRING:

• All internal wiring shall terminate on clearly identified terminal blocks.
• A wiring diagram shall be installed on the control box cover.
• Prior to shipping, heaters shall withstand tests as required by CSA.