Tubular heater specification, Specification for tubular heaters - long form, Thermolec – Thermolec Application &Technical Notes User Manual

Page 43: Tubular heaters

Advertising
background image

S

PECIFICATION

FOR

TUBULAR HEATERS

Long Form

Supply where indicated in these specifications CSA (NRTL/C) approved tubular duct heaters as manufactured by
THERMOLEC.

1- CONSTRUCTION:

• Frame shall be corrosion-resistant and made of galvanized steel of suitable gauge as required by CSA.
• Heating elements shall be tubular type made of heavy gauge Incoloy 800 filled with compacted magnesium oxide

insulating powder.

• Above 277 Volts or 30KW, each tube shall be of "U" type and shall be removable through the control box without

removing the heater from its ductwork.

2- SAFETY CONTROLS:

• Heaters shall be equipped with fail-safe automatic reset disc-type thermal cut-out(s) located in the top frame

component above the heating elements.

• In addition to the automatic reset cut-out, heaters of 30 KW and less, rated for voltages below 300 volts shall be

equipped with a fail-safe manual reset disc-type thermal cut-out, semi-recessed in the terminal box, facing the
heating element hairpin as required by CSA.

• The sensing element of the cut-out shall be stream mounted, shall be shielded from mechanical damage and shall

face the center portion of the heating section so as to make the heater non-sensitive to air flow direction.

• Cut-outs shall de-energize the heater in case of insufficient air flow.
• For maintenance and safety purposes, a built-in disconnect shall be supplied to switch the power off at the heater

location.

• Load fuses shall be supplied as required by NEC (National Electrical Code).

3- AIR FLOW:

• Duct heaters shall be non-sensitive to air flow direction and interchangeable for horizontal or vertical ducts.

4- MOUNTING METHOD:

• Heaters shall be ST slip-in type or model FT flanged type, as shown on the plans or on the heater schedule.
• Slip-in heaters shall be suitable for insertion into the duct through an opening on its side and shall have a flange for

securing it to the duct side.

• Flanged heaters shall be suitable for attaching to matching flanges on the duct.
• Mounting flanges on both models shall be independent of the terminal box so as to allow installation without opening

the box or drilling into it.

5- SIZE & CAPACITY:

• Heater size, volts, phase kilowatt and number of control stages shall be as per heater schedule.

TUBULAR HEATER SPECIFICATION