Safety precautions – MAHLE RTI TC670V User Manual

Page 5

Advertising
background image

RTI Technologies, Inc.

Page 4

SAFETY PRECAUTIONS

!

Recover, Recycle, and Charge only the refrigerant for which the machine is configured.

!

Wear safety glasses and protective gloves. Refrigerant has a very low boiling point and can
cause frostbite.

!

Follow the TC670V operating procedures sequentially to avoid prematurely disconnecting hoses
or opening valves which may release refrigerant to the atmosphere.

!

Do not expose the TC670V to moisture or operate in wet areas.

!

Use the TC670V in locations with mechanical ventilation that provides at least four air changes
per hour.

!

Hoses used with the TC670V must have shutoff devices within 12 inches of the connection
point to the system being serviced to minimize the introduction of Non-condensable Gas (Air)
into the TC670V and the release of refrigerant when being disconnected.

!

Disconnect power before performing any maintenance or service on the TC670V.

!

Avoid using an extension cord with the TC670V. If necessary, use a good condition, UL listed,
3-wire grounded, #14 AWG extension cord of the shortest possible length.

!

Connect the TC670V to a properly protected, grounded receptacle. Do not over load the circuit.

!

Do not allow the TC670V to remain unattended in the Charge Mode with power On. The
Charge Cylinder Heater will be energized creating a high pressure condition.

NEVER TURN THE CYLINDER UP-SIDE-DOWN.

DO NOT CONNECT THE TC670V TO THE LIQUID SIDE OF ANY
A/C SYSTEM WITH A CAPACITY GREATER THAN 4 LBS.

REFRIGERANT IN A/C SYSTEMS HAVING LARGER CAPACITIES
MUST BE RECOVERED FROM THE VAPOR SIDE ONLY.

NEVER CONNECT THE TC670V TO THE LIQUID PORT OF A

CYLINDER OF REFRIGERANT TO FILL THE TC670V CHARGE CYLINDER.

FAILURE TO FOLLOW THE ABOVE MAY CAUSE THE TC670V COMPRESSOR TO
FAIL AND VOID THE WARRANTY.

Advertising