CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM


6.

Self-diagnostics, self-test and proactive fault detection;


7.

Communication to the host server via serial port;


8.

Communication to the Network Interface Card or another SmartSlot accessory
card if equipped.


9.

Etc.

B.

Display/Control Unit: A display/control comprised of 16 LEDs and 2 pushbutton
switches is located on the front side of the UPS. The display/control unit may be turned
90 degrees clockwise or counterclockwise to accommodate for the way the UPS is
mounted: as a tower UPS or as a rack-mounted UPS.

C.

The pushbutton switches located at the Display/Control Unit: The following controls
functions can be accomplished by use of the pushbutton switches located at the
Display/Control Unit:

1.

Turn the UPS on;


2.

Turn the UPS off;


3.

Initiate self-test in order to test battery condition;


4.

Silence audible alarm;


5.

Cold start.

6.

Displaying input RMS voltage on the battery capacity LED bar graph.

D.

Bypass switch: On the rear panel of the UPS (models rated 5000VA and higher) there’s
a switch that when engaged forces the UPS into bypass state provided the input voltage
and frequency are within acceptable limits.

E.

EPO switch: The UPS is equipped with Emergency Power Off (EPO) terminal which
can be wired so as to provide means to instantaneously de-energize the UPS and its load
from a remote location in case of emergency.

F.

Data displayed on the Display/Control Unit: The following indicators are available on
the Display/Control Unit:

1.

The UPS load LED bar;


2.

The UPS is online;


3.

The UPS is on battery;


4.

The UPS is in bypass;


5.

The UPS is overloaded;

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM