USE CAUTION TO NOT MOVE CONNECTING TUBES AS LEAKS COULD DEVELOP

! Turn off Filter By-pass Valve by turning yellow handle on rear of cabinet to VERTICAL

position.

! Operate the RR750X in Recover Mode and check for leaks. Repair as necessary.

! Record Hour Meter reading on label provided. Replace the Filter-drier cover.

AFTER EVERY 500 HOURS OF OPERATION

Replace Acid Filter as described in the following steps:

! Cap the RR750X Inlet Port.

! Turn on the Main Power Switch and allow RR750X to run until Compressor-On Light goes

off.

! Turn off the Main Power Switch.

! Remove the smaller filter cover on rear of cabinet.

! Remove and replace the Acid Filter. Note direction of flow indicated on the new Acid Filter.

The arrow must point DOWN.

! Operate the RR750X in Recover Mode and check for leaks. Repair as necessary.

! Record Hour Meter reading on label provided. Replace the Acid Filter cover.