Scheduled maintenance, Combo filter replacement – MAHLE RTI TX600 User Manual

Page 13

Advertising
background image

RTI Technologies, Inc.

Page 12

SCHEDULED MAINTENANCE

AFTER EVERY 10 HOURS OF OPERATION...

Clean the Condenser to maintain high efficiency performance of the TX600. Disconnect power and
remove the Rear Access Cover. Blow compressed air through the cooling fins of the Condenser to
remove any debris.

Replace the Rear Access Cover before applying power to the TX600.

COMBO FILTER REPLACEMENT

Two Combo Filters are installed inside the TX600.

The Outlet Combo Filter can be identified by the presence of insulation around the outside. This
Outlet Combo Filter must be changed after every 50 hours operation.

The Inlet Combo Filter does not have insulation around the outside. This Inlet Combo Filter must
be changed after every 25 hours operation.

Replace Combo Filters as follows:

Remove Rear Access Cover.

Disconnect Flare Adaptor Fittings at top and bottom of Filters.

Remove the mounting screws and remove Filters.

Remove the black insulation from the one filter and re-install on the new Filter.

NOTE...

Remove the Valve Core from bottom port of the Filter which has the black
insulation installed around it. This Filter has a copper tube connected to the
bottom port for returning oil to the Compressor.

Install new Filters using the hardware removed earlier.

Connect Flare Adaptor Fittings to top and bottom of Filters.

Check for leaks and repair as required.

Replace Rear Access Cover.