FIGURE I Connections For Recycle Mode

RECYCLE MODE

(Refer To Figure I)

Install Tee Fitting on VAPOR Port of Refrigerant Cylinder. Remove Valve Core, if any, from Tee
Fitting.

Connect Pressure Gauge on branch of Tee Fitting.

Connect end of Yellow Service Hose with Shut-off Valve to Tee Fitting. Install Anti-Blowback
Valve on other end of hose and connect to Outlet of TX600 (Refer to Figure I). Leave Hose
connected to Outlet unless TX600 repair or transport is required.

Connect Yellow Service Hose from Inlet Port of TX600 to center port of Gauge Manifold. Shut-off
Valve must be on end connected to Gauge Manifold (Refer to Figure I). Leave Hose connected to
Inlet unless TX600 repair or transport is required.

WARNING...

Refrigerant Cylinder must have an Overfill Protection (OFP) Device.

Disconnect Power Cord from power source while connecting the OFP
(Overfill Protection) Device to avoid bodily injury due to electrical shock.

Connect Yellow Cable from rear of TX600 to OFP Device on Refrigerant Cylinder. A receptacle
on the lower rear of the TX600 can be used to store the Plug when not connected to OFP Device on
Cylinder during non-use to prevent debris from collecting inside the housing.

CAUTION...

Do not force plug into OFP Device. Look at pins in plug and align
them with sockets on OFP Device.

Attach High and Low Gauge Manifold Hoses to A/C system per manufacturer's instructions.