Flush Mount Rack Kit Installation Procedure

3 of 10

53-1002127-04

Contents

This document provides instructions to install a Brocade VDX 6710-54 (1U), VDX 6720-24 (1U), VDX 6730-32 (1U),
VDX 6720-60 (2U), VDX 6730-76 (2U), or VDX 6740 (1U)

switch in a telecommunications (Telco) rack using the

Flush Mount Kit. The document is organized as follows.

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Installation requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Tool requirements and parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Introduction

The supported switches are listed in

Table 1

.

Installation requirements

Allow 15 to 30 minutes to complete this procedure. Note the following requirements to ensure correct installation
and operation:

Verify that the additional weight of the switch does not exceed the rack’s weight limits.

Ensure that an electrical branch circuit with the following characteristics is available:

-

Required voltage and frequency as indicated in the hardware reference manual (200-230 VAC is always
preferred).

-

Protection by a circuit breaker in accordance with local electrical codes.

-

Supply circuit, line fusing, and wire size that conform to the electrical rating on the switch nameplate.

-

Grounded outlet compatible with the power cord and installed by a licensed electrician.

Ensure that all equipment installed in the rack is grounded through a reliable branch circuit connection. Do not
rely on a secondary connection to a branch circuit, such as a power strip.

Ensure that the rack is mechanically secured to ensure stability.

Ensure that the air temperature at the fan inlet is less than 40

o

C (104

o

F) during switch operation.

Ensure that the airflow available at the air vents meets the minimum requirements for the switch.

TABLE 1

Supported switches

Switch height

Switch model

1U

Brocade VDX 6710-54
Brocade VDX 6720-24
Brocade VDX 6730-32
Brocade VDX 6740

2U

Brocade VDX 6720-60
Brocade VDX 6730-76