AIR VANTAGE® 500 CUMMINS

A-7

INSTALLATION

A-7

2. Take necessary steps to assure load is limited to the capacity

of the AIR VANTAGE® 500 by installing a 50 amp, 240 VAC
double pole circuit breaker. Maximum rated load for each leg
of the 240 VAC auxiliary is 50 amps. Loading above the rated
output will reduce output voltage below the allowable -10% of
rated voltage which may damage appliances or other motor-
driven equipment and may result in overheating of the AIR
VANTAGE® 500 engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-50) to the

double-pole circuit breaker using No. 6, 4 conductor cable of
the desired length. (The 50 amp, 120/240 VAC plug is
available in the optional K802R plug kit.)

4. Plug this cable into the 50 Amp 120/240 Volt receptacle on the

AIR VANTAGE® 500 case front.

Figure A.2 Connection of the AIR VANTAGE® 500 to Premises Wiring

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE