0 specifications – APC 600 User Manual
Page 38

36
9.0 Specifications
9.1 Input
UPS version (Vac):
100
120
220/230/240
Nominal input voltage (Vac):
single phase
100
120
230
Nominal input frequency:
50 or 60 Hz.
Internally selected by microprocessor.
Input protection:
8 Amp
7 Amp
5 Amp
Push-to-reset circuit breaker.
Input connections:
IEC 320 male inlet coupler. 120 and 100 Vac versions
include 6 ft (2 m) line cord, with a NEMA 5-15P three pronged plug.
9.2 Transfer characteristics
Frequency limits for on-line operation:
50 or 60 Hz, ±5%
Lower input voltage
†
, on-line operation:
80 Vac
90 Vac
173 Vac
Upper input voltage
†
, on-line operation:
110 Vac
132 Vac
253 Vac
SmartBoost operation line voltage
†
(Vac):
80–90
90–103
173–196
Transfer time:
2 ms typical;
(1 ms is 0.001 seconds).
4 ms maximum.
† Note that these are the default values. Transfer parameters may be
configured using UPS monitoring software.
9.3 Output characteristics
On-battery output voltage (Vac):
100 ±5% 115 ±5% 225 ±5%
Maximum output current:
6 Amp
5.2 Amp 2.7 Amp
Maximum load:
600 VA or
400 W at 0.67 power factor
On-battery Frequency:
50 or 60 Hz, ±0.1 Hz.
Synchronized to mains frequency during brownout.
On-battery waveshape:
sinewave.
Protection:
Overcurrent and short-circuit protected, latching shutdown
upon overload.
Output connections:
100 and 120 Vac versions have four NEMA 5-15R
receptacles. 220/230/240 Vac version has four IEC 320 output couplers
and includes two 6 ft (2 m) output cords with IEC 320 couplers and one
IEC rewireable plug adapter.