A-7

INSTALLATION

VANTAGE 500 DEUTZ

A-7

2. Take necessary steps to assure load is limited to

the capacity of the VANTAGE 500 DEUTZ by
installing a 50 amp, 240 VAC double pole circuit
breaker. Maximum rated load for each leg of the
240 VAC auxiliary is 50 amps. Loading above the
rated output will reduce output voltage below the
allowable -10% of rated voltage which may damage
appliances or other motor-driven equipment and
may result in overheating of the VANTAGE 500
DEUTZ engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type

14-50) to the double-pole circuit breaker using No.
6, 4 conductor cable of the desired length. (The 50
amp, 120/240 VAC plug is available in the optional
K802R plug kit.)

4. Plug this cable into the 50 Amp 120/240 Volt recep-

tacle on the VANTAGE 500 DEUTZ case front.

Figure A.2 Connection of the VANTAGE 500 DEUTZ to Premises Wiring

240 Volt-

60 Hz.-

3-Wire-

Service

POWER-

-

COMPANY-

-

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES-

DISCONNECT AND-

SERVICE-

OVERCURRENT-

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE SEE-

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE-

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP-

240 VOLT

DOUBLE-

POLE-

CIRCUIT-

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240-

VOLT PLUG-

NEMA TYPE 14-50

50 AMP, 120/240 VOLT-

RECEPTACLE