5. FEATURE SETTING

To understand more about the unit features, read the following section and follow the instructions

to make changes to the desired setting.

Default Factory Setting:

In (Inverter): In1- inverter enabled in standby mode with load sense off

Cu (Charger): 55A – charger enabled (55A for 32326)

AL (Alarm): AL1 – alarm enabled

Sd (UV shutdown): SdL – Under voltage shutdown set to low setting

bAt (Battery type): FLo – Flooded typed

Cb (Maximum current): Cb3 – Maximum Shore Power Current draw is 30A

Understanding the Unit Settings

Inverter Setting

In0

Inverter is disabled, unit will not provide backup function when utility power is not

available

In1

Inverter is set to standby mode with power save mode OFF. Unit will provide

backup function when utility power is not available

In2

Inverter is set to standby mode with power save mode ON. Unit will provide

backup function only when utility power is not available AND the load connected

to the output is >10W.

Note: Unit will turns ON every 10 s to check on the power consumption.

Charger Current Setting

5A – 40A

5A – 55A

Bulk/Float current setting:

32326: 5A/1.5A, 15A/3A, 35A/4A, 55A/6A

Battery Type and Voltage Setting (Bulk/Absorption/Float)

FLo

Flooded: 14.4V / 14.4V / 13.5V

GEL

GEL: 14.2V / 14.2V / 13.8V

AG

AGM: 14.3V / 14.3V / 13.4V

Fi

Fixed: 13.5 Vdc fixed voltage

Battery Under Voltage Setting

SdL

Battery under voltage setting is set to LOW (setting used for normal operation)

Under voltage alarm: 11.0 Vdc

Under voltage alarm recovery: 11.3 Vdc

Under voltage shutdown: 10.5 Vdc

Under voltage recovery: 12.0 Vdc

SdH

Battery under voltage setting is set to HIGH (setting to avoid battery over

discharge when connected to car start battery)

Under voltage alarm: 12.1 Vdc

Under voltage alarm recovery: 12.3 Vdc

Under voltage shutdown: 11.8 Vdc

Under voltage recovery: 12.6 Vdc

Alarm Setting

AL0

Fault and warning audible alarm is disabled. Display panel only shows error code

and audible alarm will not sound.

AL1

Audible alarm will sound when fault or warning occurs.

Maximum Shore Power Current Draw Setting

32326

AC Load Current

Charger Current

Cb1

Set the maximum current draw from shore power to 15A. The maximum current

draw from unit is set to match with the shore power circuit breaker rating to avoid

tripping of the shore power circuit breaker during the by-pass mode. Battery

charging current will automatically reduce when there is a high demand on AC

load during the by-pass mode.

>11Aac

5 Adc