SANDPIPER RuppTech Stroke Counter/Batch Control User Manual
Page 5

Batch Control/Stroke Counter
Page 5
Batch-sc-rev0611
520-180-000 3/02
Batch Control / Stroke Counter
Page 5
Selecting & Storing a Preset Count
To initially store or change a Preset Count value, select one of the ten program
storage locations (P0 through P9). Press and hold the Increase Digit button to
display the current register location. The display will show P0 through P9 for these
locations. Press and release the Increase Digit button to sequence through to
the location which will store the new Preset Count value, Release the Increase
Digit button.
After selecting the program storage location, press and hold the Preset Count
button until the following sequence is completed. Press the Reset button to reset
the display to a zero value. The digit position available for setting will flash. Press
and release the Increase Digit button to change the digit to the required value.
Repeat the process using the Digit Select button until each digit location is set
as required.
Resetting the Total Count
Press and hold in the Total Count button. Press and release the Digit Select/
Reset button. The display will reset to zero.
Resetting the Preset Count
Press and hold in the Preset Count button. Press and release the Digit Select/
Reset button. The display will reset to zero. To reprogram, refer to the procedures
outlined in Selecting & Storing a Preset Count.
Functions (with the pump running)
START Button - NOTE: Use a momentary contact switch when using a remote
start/stop control.
This button is used only when the control is utilized as a Batch Controller. In
this mode of operation, the control is used with an electric solenoid air valve, which
controls the air supply to the pump. Pressing this button starts the pump. The
control has an internal connection for utilizing an external or remote
START button.
STOP Button - NOTE: Use a momentary contact switch when using a remote
start/stop control.
This button is only used when the control is utilized as a Batch Controller.
Pressing this button stops the pump. The unit can be restarted by pressing the
START button. The control has an internal connection for utilizing an external or
remote STOP button. When a Preset Count has been stopped before completion,
the display valve will not flash. This is to show the count has been stopped. When
the pump stops after completing a Preset Count, the display panel will flash.
PROGRAMMING QUICK
REFERENCE
Programming & Storing a Preset
Count
1. Press and hold Preset Coun
t
a. Press Reset to reset the
display to zero.
b. Press and release Increase
Digit to change the flashing
digit.
c. Press Digit Select until each
digit is set.
Resetting the Total Count
1. Press Total Count.
a. Press and release Reset.
Resetting the Preset Count.
2. Press and hold Preset Count.
a. Press and release Digit
Select/Reset.
Selecting a Program Storage Area
1.Press and release Increase
Digit to sequence through
program storage areas
(P0 through P9).
2.When the desired storage area
appears, proceed with
programing and storage.