Transportation damage, Unpacking the unit, Operating instructions – SoleusAir SG-TTW-12ESEZ-26 User Manual

Page 4

Advertising
background image

IMPORTANT NOTE TO THE OWNER

This equipment is to be serviced by professionally trained

personnel only. If this equipment is improperly installed,

adjusted or altered by an unqualified person, a safety

hazard may result.

IMPORTANT NOTE TO THE SERVICER

Read this manual and familiarize yourself with the specific

items which must be adhered to before attempting to

service this unit. The precautions listed in this manual

should not supersede existing practices but should be

considered as supplemental information.

Transportation Damage

All units are securely packed in shipping containers ap-

proved by the National Safe Transit Association.

The carton

should be checked upon arrival for external damage. If

damage is found, immediately make a written request for

inspection by the carrier’s agent.
In the event of damage:

1. Note on the delivery receipt any visible damage to

shipment or container.

2. Notify carrier promptly and request an inspection.
3. File the claim with the following supporting documents

within the six month statute of limitations.

a. Original Bill of Lading, certified copy, or indemnity

bond.

b. Original paid freight bill or indemnity.
c. Original invoice or certified copy, showing trade and

other discounts or reductions.

d. Copy of the inspection report issued by carrier’s

representative at the time damage is reported to the

carrier.

The carrier is responsible for making prompt inspection of

damage and for a thorough investigation of each claim.

The

distributor or manufacturer will not accept claims from

dealers for transportation damage.

Unpacking The Unit

1. Cut the carton banding and open the carton.
2. Remove the literature, hardware pack, upper styrofoam

shipping blocks, and styrofoam corner posts.

3. Remove the front assembly.
4. Lift the unit from the remaining carton.
5. Dispose of the cardboard and styrofoam at an approved

Recycle Center. Check all contents for damaged or

missing parts. In case of concealed damage, notify the

carrier as soon as possible—preferably within 5 days.

Refer to step 3 of the

Transportation Damage section if

damage or missing parts are noted.

Operating Instructions

Check the data specification plate and ensure the proper

voltage and current rating for the type of power plug on the

unit is available. DO NOT REMOVE THE GROUNDING

PRONG FROM THE POWER CORD. See Figure 1 for the

types of acceptable plugs. Do not use an extension cord

for the installation of this product.

Refer to the data

specification plate for electrical requirements.

1

3 amp

Figure 1

LCDI or AFCI Power Cords - Underwrites Laboratories

and the National Electric Code (NEC) now require

power cords that sense current leakage and can open

the electrical circuit to the unit on units rated at 250

volts or less. In the event that unit does not operate,

check the reset button located on or near the head of

the power cord as part of the normal troubleshooting

procedure.

LCDI power Cord

VOLTAGE MEASUREMENTS

Before connecting the unit, measure the supply voltage.

Voltage must fall within the voltage utilization range given

in Table 1.

Operating Voltage

Unit Voltage

Rating

Voltage Utilization Range

Minimum

Maximum

230/208

187

253

115

103

126

Table 1

Operating Voltage

1

120V

240V

240V

1

8 amp

1

5 amp

Advertising
This manual is related to the following products: