Frequency output programming, Gate time filter, Rt-30ex flow transmitter – AW Gear Meters RT-30EX User Manual

Page 27

Advertising
background image

RT-30EX Flow Transmitter

Operation and Programming Manual

27

RT-30EX User Manual, Rev. 1.7 02/07/2012

minus the MARGIN value. The programmed Limit Margin must be less than the programmed Rate
Value.

TOTAL & GRAND TOTAL Limits





TOTAL / GRAND TOTAL Value

Enter the Total or Grand Total value at which the respective Limit output should change state. When
the Total or Grand Total is reset to zero, the limit pin changes back to initial state.

Frequency output programming

The third output can only be set to output the incoming frequency. From the top Limit programming
menu, choose the Frequency Output option, press

ENT

and use the

UP

or

DN

button to turn the output

frequency on. There are no other variables to program. The output frequency is not affected by the
Gate Time filter and cannot be linearized. It is always the raw incoming frequency from the sensor.

Gate Time filter


This variable sets the sample time on the incoming frequency for the RATE displays. Programmed in
tenths of a second with an allowable range from 0.1 to 999.9 seconds, this variable affects the update of
the display and analog output, and is useful in stabilizing the display and output when dealing with
fluctuating flow rates. Setting the Gate Time to zero (0) disables the Gate Time filter and all data is
updated at an internal default rate of approximately 0.02 seconds. If the Gate Time filter is active (any
non-zero value) any run mode screen affected by the filter will show ‘GT’ in the lower right hand corner
of the screen.

Total Value

00000.00 GAL

Grand Total Value

00000.00 GAL

ENT

ENT

TOTAL Limit

GRAND TOTAL Limit

Select Limit
Frequency Output
Select Limit type
> ON

ENT

Gate Time Filter
(in seconds)

001.0

ENT

Figure 35: Frequency Output programming

Figure 36: Gate Time variable

Figure 34: Total & Grand Total limit variables