Model FP-100

FP-100 Instruction Manual

Rev. 0.0

Page 24 of 30

Faulty 4-20mA Output (F03)

Check that wiring is properly connected at terminal board and through to controller inputs.
The 4-20 output loop must be closed (resistance of < 750 ohms).
If the 4-20mA signal output is 0mA to 2mA, there is an ITM fault.
Swap with new ITM to determine if the ITM is faulty.