1.4 I

NSTALLATION

1. Securely mount the 412B enclosure in accordance with the drawing in figure 1.

N

No

ottee::

Reference figure 2 for wiring terminations.

2. Connect 117VAC input to the terminal strip labeled “VAC IN” (L1, N, GND).

3. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+ and –).

4. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate

field wiring from sensors to the 412B motherboard. Terminals are labeled “SENSOR” (MA, + and —).

5. If applicable, terminate the discrete 4-20 mA outputs to external device(s). Terminals are labeled “4-20 mA OUT”

(+ and —).

6. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “RS-485” (A+, B–,

and Shield).

Model 412B Rack Mount Control Enclosure PG.4

L1 In

Fuse

L1 - BLK

N - WHT

GND - GRN

BLK

16ga x 9"

BLK

16ga x 9"

Power

Switch

RED

16ga x 9"

RED

16ga x 9"

TAN

22ga x 9"

TAN

22ga x 9"

BLK

16ga x 9"

BLK

16ga x 9"

D2 6A 50V

RED

BLK

Power Supply

Pin 5 Com

Pin 7 +

Pin 2 N

Pin 3 L

16ga x 6"

P1

TB1

TB2

N In
GND In
+DC In
–DC In
+DC Out
–DC Out

Pin 1

16ga x 6"

16ga x 6"

16ga x 6"

16ga x 6"

P2

P3

P4

P5

D1 6A 50V

Power

Supply
DC Out

Power

Supply

VAC In

PS80-12B Power Supply Schematic/Wiring Diagram