Figure 8 modbus™ gas sensor connections, Figure 9 model rl-4 relay module – Detcon 6400-N1P User Manual
Page 11

1600/6400-N1P
1600/6400-N1P- Instruction Manual
Rev. 1.1
Page 7 of 38
RS-485 Modbus Gas Sensors
Connect the five wires from the Modbus™ gas sensors (Detcon Model 600 and Model 700 Series types) to the
din rail mounted terminals labeled RS-485 “A”, “B”, and “Shld” and VDC “+” and “-”. Note: the controller
power supply is only capable of handling 3-3.5Amps accumulative. If the external sensors plus the controllers
internal modules exceeds this rating, only three wires (RS-485 “A”, “B”, and “Shld”) should be used and a
remote DC power source should be utilized to provide DC power for the remote mounted gas sensors.
NOTE: A 120
Ω end of line resistor should be installed on the last gas sensor in the serial loop to enhance
communications reliability.
Figure 8 Modbus™ Gas Sensor Connections
Relay Output Contact Modules
There are four Form ‘C’ 5 Amp relay contacts in each Model RL4 module. These can be used to fire
annunciating devices or as signal inputs to other control devices. Connect to the relay contacts of the Model
RL4 module as shown Figure 9. Note that the Amp rating of the relay contact should not be exceeded.
Figure 9 Model RL-4 Relay Module
4-20mA Output Modules
There are four 4-20mA outputs in each Model AO-4 module. These can be used as signal inputs to other
control devices. Connect to the AO-4 modules as shown in Figure 10: