Detcon 6400-N1P User Manual

Page 8

Advertising
background image

1600/6400-N1P

1600/6400-N1P- Instruction Manual

Rev. 1.1

Page 4 of 38

WARNING: Do not attach more devices to the controller power supply than the power supply has the
capacity for, as damage may occur to the controller and the warranty will be void. Modules and
sensors attached to the unit that exceed this power rating should be powered by an external power
supply capable of handling the extended load.


The secondary serial RS-485 port from the controller can be connected to a PLC, PC/HMI, DCS, or other
Modbus™ master polling serial communications device, refer to Section 7.0 Secondary Modbus™ Port.

Optionally, (the RS-485 output is standard, but can be replaced with the optional RS-232) connect the RS-232
output wiring to the D-sub connector located on the optional RS-232 Serial Communications PCB. (Refer to
Figure 4.) Use standard RS-232 cable and D-Sub connector. This serial output may be connected to a PC or
external serial printer.

No Comm

C

NO

NC

Fault Relay PCB

J1

Serial Communications

Primary

PCB

S
B
A

A
B
S

Secondary

J3

J7

RS-232

Serial Communications

RS-485

PCB

S

B

A

J3

(Optional) RS-232

RS-485

Rel

a

y

J2

500-003053-001

500-003054-000

500-005081-000

RS-485

Input

Output

Port

Port

Input Port

Output Port

are brought out to the

Relay Contact connections

Terminal Block via J1

Figure 4 No Comm. Fault Relay and Serial Communications PCB’s


The No Communications Fault Relay is connected to a set of Terminal Blocks on the din-Rail (Figure 5 and
Figure 4.) The Terminal Blocks are labeled “NO COMM” “C”, “NO” and “NC”. The No Comm. Fault Relay
PCB, mounted on the back of the controller PCB, will de-energize the on board relay in the event there is a
‘No Communication Fault’ condition with any activated device. A ‘No Communication Fault’ condition will
‘short’ the common and normally closed contacts and create an open between the normally open and common
relay contacts of the on-board relay. This is required for fail-safe operation. There is a two-minute delay
before any active device will trigger a no communication condition.

The unit includes connections for a Remote Alarm Reset Switch. A set of Terminal Blocks is supplied for the
connection of a Remote Alarm Reset Switch that can be mounted anywhere outside the unit. The Remote
Alarm Reset incorporates a set of normally closed contacts that cause the unit to reset the Alarms when contact
is broken. To install a Remote Reset Switch the jumper between terminal blocks 8 and 9 (labeled “Remote
Reset”) must be removed and the switch wired to these terminals. Connect only a normally closed switch to
these terminal blocks. If more than one switch is to be connected, the switches must be connected in series.

NOTE: The Remote Alarm Reset switch should be a ‘Normally Closed’ Switch and should be wired as
such. Failure to wire the switch correctly will cause the Enclosure Alarm Reset and all subsequently
connected Remote Alarm Reset Switches to be non operational.

Advertising
This manual is related to the following products: