Synchronization of visible outputs, Synchronization of visible and audible outputs – Edwards Signaling EBPS Remote Booster Power Supply User Manual
Page 50

44
Remote Booster Power Supply Technical Reference Manual
Synchronization of visible outputs
In the figure below, all visible output circuits on each BPS activate with a one
second delay. This requires that the BPSs be connected in parallel through their
sense circuits.
Figure 23: Synchronization with a one second output activation delay
1
2
3
4
5
6
7
8
9
10 11 12 13
(1)
(2)
(3)
(4)
(5)
(1)
On Sense Off
(2) Output booster 1
(3)
Output booster 2
(4) Output booster 3
(5) Output
booster
n
Sync diagram key
Strobe flash
Audible
tone
Synchronization of visible and audible outputs
One-second delay of outputs
In the figure below, all visible and audible circuits are synchronized with a one
second output activation delay when the BPSs are connected in parallel through
their sense circuits.
Note:
Delay time is controlled by DIP switch SW1-4. See “Setting the DIP
switches” for more information.