Features and functions, Terminals, Switches – Edwards Signaling ANSZS4B User Manual

Page 2: Jumpers

Advertising
background image

2 / 4

P/N 3101185 • REV 02 • REB 28FEB13

Features and functions

Figure 1 shows the location of the terminal blocks, zone

selection switches, configuration jumpers, and PTCs. This

topic describes the functions of each component.

Figure 1: Features of the ANSZS2A and ANSZS4B cards

Terminals

Table 1: Terminal descriptions
Terminal

Description

TB1

Speaker output terminals, at either 25 or 70 Vrms, per

PTC setting.
ANSZS4B: Output terminals for four zones. (Class B,

Style Z.)
ANSZS2A: Output and return terminals for two zones.

(Class A, Style Y.)

Polarity ANSZS4B

ANSZS2A

TB1-1

+

Zone 1 output

Zone 1 output

TB1-2

Zone 1 output

Zone 1 output

TB1-3

+

Zone 2 output

Zone 1 return

TB1-4

Zone 2 output

Zone 1 return

TB1-5

+

Zone 3 output

Zone 2 output

TB1-6

Zone 3 output

Zone 2 output

TB1-7

+

Zone 4 output

Zone 2 return

TB1-8

Zone 4 output

Zone 2 return

TB2-1

Signal source +

TB2-2

Signal source −

TB2-3

PTT (push to talk) signal

Terminal

Description

TB2-4

24 Vdc power supply +

TB2-5

Alarm active signal

TB2-6

Circuit negative

TB2-7

Aux. trouble relay N.O. [1]

TB2-8

Aux. trouble relay C.

TB2-9

Aux. trouble relay N.C.

TB2-10

Supervisory circuit input

TB2-11

Supervisory circuit input

TB3-1

Supervisory circuit output or EOLR

TB3-2

Supervisory circuit output or EOLR

TB3-3 to 7

Optional zone activation (pull-down) [2]

TB3-3

All Call activation

TB3-4

Zone 4 activation

TB3-5

Zone 3 activation

TB3-6

Zone 2 activation

TB3-7

Zone 1 activation

[1] See “Specifications” for more information on the Aux. trouble relay

[2] See J1 settings under “Jumpers” for optional zone activation

Switches

Switches S1 through S4 provide manual zone activation when

an operator is in attendance. Switch S5 activates all zones (All

Call) on all interconnected ANSZS2A or ANSZS4B zone

splitters. Switching S5 on any zone splitter generates an all call

for all zone splitters in the system.

Caution:

Do not leave a zone switch turned on when

unattended, as this leaves the zone unsupervised.

Table 2: Switch descriptions
Switch

Description

S1

Zone 1 activation

S2

Zone 2 activation

S3

Zone 3 activation

S4

Zone 4 activation

S5

All Call activation

Jumpers

Table 3: Jumper settings
Jumper

Setting

J1

Determines zone activation on alarm active (0 Ω

jumper)

Installed

All Call operation on alarm active

Removed

Zone-by-zone activation using pull-down inputs on TB3

J1

TB1

TB2

TB3

S1

S2

S3

S4

S5

+

+

+

+

1

2

3

4

5

6

8

7

1
2
3
4
5
6
7
8
9

10

11

1 2 3 4 5 6 7

2

PTCs

4

6

8

Advertising
This manual is related to the following products: